Cod. +030221881 rel. 1.0 - 11/02/2000 26
)GSRVWGULSSLQJRIIDFWLYHERWKZKHQ) DQG) 
The fans, after the defrost, can be stopped for a further period (in minutes) defined by the value of
)G
. This is useful to allow the
evaporator to return to operating temperature after the defrost, thus avoiding forcinghot’ air into the refrigerator. In the case of
management by fan controller, the time
)G
does not need to be selected, in that the controller makes the fans start again when the
evaporator reaches operating temperature. If the fan controller is active (
)
=1), assigning
)G
a value other than zero means the
fans
VWD\RII
for a time equal to the value of
)G
, irrespective of the temperature of the evaporator.
Def.:
)G
= 1 minute post-dripping stop. Available on: PJ32C.
'LDJUDPVXPPDULVLQJRSHUDWLRQRIWKHHYDSRUDWRUIDQV
fan management
fans always
on?
(F0=1) no yes (F0=0)
fans managed by fan controller
fans on when evaporator
temperature <F1-AD
fans off when evaporator
temperature >F1
fans off when
compressor
off?
fans off when
compressor
off?
fans always off
during dripping (dd)
and post-dripping (fd)
yes
yes
no
no
F2=1
F2=1
F2=0
F2=0
)LJ
:DUQLQJ
for correct operation the post-dripping phase must be preceded by the dripping phase for a time greater than zero
(
GG
>0).