G GHIURVWSDUDPHWHUV
G
type of defrost (0= heating element,1= hot gas,
2= water or element by time, 3= hot gas by time)
&
0 3 flag 0
G,
interval between two defrosts F 0 199 hours 8
GW
end defrost temperature F -50 +127 °C/°F 4
G3
maximum defrost duration or effective duration when
G
=2 or 3 F 1 199 min 30
G
defrost at instrument on (0=no, 1=yes)
&
0 1 flag 0
G
defrost delay when the unit is turned on or from digital input (
$
or
$
=4)
&
0 199 min 0
G
display off during defrost (0=no, 1=yes)
&
0 1 flag 1
GG
dripping time after defrost F 0 15 min 2
G
alarm bypass time after defrost F 0 15 hours 1
G
priority of defrost over compressor protection (0=no, 1=yes)
&
0 1 flag 0
G
display defrost probe temperature F - - °C/°F -
G&
time basis (0=hours/min, 1=min/s)
&
0 1 flag 0
$ DODUPSDUDPHWHUV
$
alarm and fan differential
&
0 +19 °C/°F 0
$/
low temperature alarm (indicates the maximum variation allowed in respect to the
Set Point). If set = 0 excludes the low temperature alarm
F 0 +127 °C/°F 0
$+
high temperature alarm (indicates the maximum variation allowed in respect to the
Set Point). If set = 0 excludes the high temperature alarm
F 0 +127 °C/°F 0
$G
temperature alarm delay
&
0 199 min 0
$
digital input configuration
&
0 4 - 0
$
detection time delay for the alarm input (
$
= 1)
&
0 199 min 0
) IDQSDUDPHWHUV
)
fan management: 0 = fans always on except specific phases (see parameters
)
,
)
, and
)G
); 1=fans controlled according to the temperature of the evaporator and
excluding the phases
)
,
)
,
)G
.
&
0 1 flag 0
)
fan on temperature: if
)
=1;
)
is the fan ON Set Point (evapor. T < Set Point(
)
))
F -50 +127 °C/°F 5
)
fans off with compressor off (0=no, 1=yes).
&
0 1 flag 1
)
fans off in defrost (0=no, 1=yes).
&
0 1 flag 1
)G
off in post dripping. F 0 15 min 1
+ RWKHUVHWWLQJV
+
serial address 0 199 - 1
+
PJ32S 0=T op.; 1=S op. with defrost
PJ32C selection of alarm relay operation
0=alarm normally not energised, 1=alarm normally energised
&
0 1 flag 1
+
0=buttons disabled;
&
0 1 flag 1
+
only PJ32S 0=buzzer enabled 1=buzzer disabled
&
0 1 flag 0
+
identification code (or model number) F -99 +99 10
(*)
W
external parameter (used only for the external options) F -127 +127 - -
7DE
(*):parameter
+
can only be set using the serial connection and is always visible at level F.