Physical data — English
30HR,HS UNIT AND COMPRESSOR
UNIT 30HR,HS SIZE 070 080 090 100 110 120 140 160
APPROXIMATE OPERATING
WEIGHT (lb)*
HR 4760 4945 5070 6436 6575 6714 7355 7775
HS 3305 3360 3420 4360 4420 4480 5065 5175
REFRIGERANT (R-22)
OPERATING CHG (lb)†
HR 104 119 129 138 146 154 172 192
HS 15.3 15.3 15.3 21.0 21.0 21.0 27.0 27.0
COMPRESSOR 06E**
(Reciprocating,
Semi-Hermetic,
1750 rpm)
HR
Ckt A 2150 A150 6175 A150 6175 F175 6175 A150 6175 F175 6175 F175 6299 F175 6299 F299
Ckt B 6175 6175 6175 6175 A150 6175 A150 6175 F175 6299 F175 6299 F299
HS
Ckt A 2250 A250 6275 A250 6275 F275 6275 A250 6275 F275 6275 F275 6299 F275 6299 F299
Ckt B 6275 6275 6275 6275 A250 6275 A250 6275 F275 6299 F275 6299 F299
Capacity Control Steps
(see page 31)
66688888
Circuit Split, % Capacity
Ckt A 57 62.5 67 50 55 50 50 50
Ckt B 43 37.5 33 50 45 50 50 50
CONDENSER PART NO. 09RP---
HR
Ckt A 043 054 070 054 070 070 070 084
Ckt B 033 033 033 054 054 070 070 084
REFRIGERANT CONN. (in. ODM)
Liquid Line
HS
Ckt A
7
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
Ckt B
7
⁄
8
7
⁄
8
7
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
Discharge Line
Ckt A 1
5
⁄
8
1
5
⁄
8
2
1
⁄
8
1
5
⁄
8
2
1
⁄
8
2
1
⁄
8
2
1
⁄
8
2
1
⁄
8
Ckt B 1
3
⁄
8
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
2
1
⁄
8
2
1
⁄
8
2
1
⁄
8
LEGEND
ODM — Outside Diameter Male
*Includes refrigerant operating charge.
†The 30HR unit is shipped with full operating charge; 30HS unit is shipped with holding charge only
(cooler operating charge shown — condenser and interconnecting piping charge must be added for
total system charge).
**Prefix (no. of unloaders): A, F = none; 2, 6 = one.
5