Table 2 - Electrical Data 
COMPLETE CHILLER 
VOLTS 
NOM 
208/230 
460 
575 
COMPRESSOR USAGEt 
Supply 
Range* 
187-253 
414-508 
518-632 
Circuit 1 
Circuit 2 
Com pressor No. 
UNIT 30 
MKW 
MCA 
MFA 
MCA 
MFA 
MCA 
MFA 
1 
2 
3 
070 
73.4 
241 
300 
108 
125 
93 
125 
2150 
A150 
6175 
080 
82.3 
270 
350 
119 
150 
105 
125 
6175 
A150 
6175 
090 
91.2 
299 
350 
130 
150 
117 
150 
6175 
F175 
6175 
100 
103.8 
148 
175 
129 
150 
6175 
A150 
6175 
A150 
HR 
, 
159 
175 
141 
175 
110 
112.7 
18 
- 
7 
- 
- 
- 
-  
6175 
F175 
6175 
A150 
120 
121.6 
207 
170 
200 
153 
175 
6175 
F175 
6175 
F175 
140 
155.8 
267 
6299 
F175 
6299 
F175 
160 
190.0 
315: 
6299 
F299 
6299 
F299 
070 
84.7 
304 
400 
128 
175 
110 
150 
2250 
A250 
. 
6275 
- 
080 
95.3 
334 
400 
144 
175 
122 
150 
6275 
A250 
6275 
- 
090 
105.9 
364 
400 \ 
160 
200 
134 
175 
6275 
F275 
6295 
- 
100 
120.0 
177 
225 
151 
175 
6275 
A250 
6275 
A250 
HS 
110 
252 
130.6 
222 
183 
- 
225 
163 
_ 200 
6275 
F275 
6275 
A250 
120 
141.2 
252 
209 
250 
175 
200 
6275 
F275 
6275 
F275 
140 
176.8 
6299 
F275 
6299 
F275 
160 
212.4 
6299 
F299 
6299 
F299 
INDIVIDUAL COMPRESSORS 
VOLTS 
208/230 
460 
575 
UNIT 30 
Comp 
06E$r 
KW 
RLA 
LRA 
MTA 
RLA 
LRA 
MTA 
RLA 
LRA 
MTA 
HR ' 
070 
thru 
120 
150 
175 
21.5 
30.4 
63 
92 
283 
446 
88 
128 
29 
40 
142 
223 
40 
56 
24 
36 
98 
164 
33 
50 
140, 
160 
175 
299 
30.4 
47.5 
92 
140 
446 
690 
128 
196 
40 
65 
223 
345 
56 
90 
36 
53 
164 
240 
50 
73 
HS 
070 
thru 
120 
250 
275 
24.7 
35.3 
82 
112 
345 
506 
114 
156 
33 
49 
173 
253 
45 
68 
29 
41 
120 
176 
40 
57 
140, 
160 
275 
299 
- 
35.3 
53.1 
112 
159 
506 
690 
156 
222 
49 
68 
253 
345 
68 
95 
41 
59 
176 
240 
57 
82 
EN
Two electrical power circuits are required. A separate 
entrance and a terminal block are provided for each 
circuit. For 30HR,HS110 units, upper value is circuit 1 
and lower value is circuit 2. For other size units, the value 
shown is same for both circuits. 
KW - 
Maximum Power Input (each compressor) 
LRA - 
Locked Rotor Amps 
MCA - 
Minimum Circuit Amps. Complies with NEC. 
Section 430-24. 
MFA - 
Maximum Fuse Amps 
MKW - 
Maximum Unit Power Input 
MTA - 
Must Trip Amps (compressor circuit breaker) 
RLA - 
Rated Load Amps 
*Supply Range - 
Units are suitable for use on electrical systems 
where voltage supplied to the unit terminals is not below or above 
the listed range limits. 
tCircuits and compressors are numbered from left to right when 
viewed from the front of the unit. Prefix: 2, 6 - has unloader, 
A, F - no unloader. 
Unbalanced 3-Phase Supply Voltage - 
Never 
operate a motor where a phase unbalance in supply 
voltage is greater than 2%. 
Use the following 
formula to determine the % voltage unbalance: 
% Voltage Unbalance = 
100 x 
max voltage deviation from average voltage 
AB = 243 volts 
BC = 236 volts 
AC = 238 volts 
Average Voltage = 
243 + 236 + 238
= 239 volts 
3  
$Models 150 and 250 are 4-cylinder compressors models 175, 
275 and 299 have 6 cylinders. 
NOTES: 
1. 
Compressor motors on all units are thermally protected by over-
temperature sensors in the discharge side of the compressor. 
2. 
Maximum allowable phase unbalance: volts, 2%; amps, 10%. 
3. 
Maximum incoming wire size: 
For all voltages: 
500 MCM for 30HR,HS070-160 
4. 
To reduce demand loading during intermediate seasons, 3-
compressor units (070-090) have a manual switch (CS) to cut 
out compressor No 2. On 4-compressor units (100-160), a 
switch (CS) is provided to cut out compressor No. 4. 
5. 
All units have a compressor starting sequence transfer switch. 
Three-compressor units: 
switch position no. 1, 
3-1-2; 
switch 
position no. 2, 
1-3-2. 
Four-compressor units: 
switch position no. 1, 
3-1-2-4; 
switch 
position no. 2, 
1-3-2-4. 
Determine maximum deviation from average 
voltage: 
(AB) 243 - 239 = 4 volts 
(BC) 239 - 236 = 3 volts 
(AC) 239 - 238 = 
Maximum deviation is 4 volts. Determine 
voltage unbalance: 
% Voltage Unbalance = 100 x 
23
9 
= 1.7% 
This amount of phase unbalance is satisfactory 
as it is below the maximum allowable of 2%. 
average voltage 
Example: Supply voltage is 240-3-60 
A B C 