it, or si 
an o
-
ne.
-
e
-
g
-
dresult of any of fife above sa ety 
devices, determine and correct the cause before 
When power is supplied to control circuit 
and control circuit switch is on, unit is ready for 
operation providing all safety devices are satisfied, 
interlocks are closed and instructions on warning 
labels have been followed. 
When START-STOP button on control panel is 
pressed to START, a white light in button comes on 
and step controller and control relays 1 thru 4 are 
energized. After a maximum of 1.5 minutes, step 
controller cycles back (in the unload direction) to 
correct cam position to begin compressor starting 
sequence. The compressors start one at a time at 
brief intervals until load requirement is satisfied. 
After completing starting sequence, controller stops 
and starts, unloads and loads compressors to main-
tain capacity control in response to water tempera-
ture controller demand. Factory cam settings on 
step controller protect compressors against rapid 
cycling. 
Complete Unit Stoppage 
can be caused by any of 
the following conditions: general power failure, 
blown fuse in control power feed disconnect, open 
control circuit breaker, START-STOP button 
pressed to STOP, open contacts in low water tem-
perature cutout, open contacts in any auxiliary 
interlock, open contacts in chilled water flow switch. 
Single
-
Circuit Stoppage 
can be caused by open 
contacts in compressor discharge temperature 
sensor, open contacts in low-pressure switch, open 
contacts in oil safety switch (when used), open 
contacts in high-pressure switch. 
Stoppage of one circuit by safety device action 
does not affect the other circuit. Besides stopping 
compressor(s), all devices listed 
except the low-
pressure switch 
will also close liquid line solenoid 
valve for that circuit. 
Restart Procedure, 
after cause for stoppage is 
corrected. (Automatic restarts are under sequence-
starting control.) 
GENERAL POWER FAILURE — Unit will 
restart automatically when power is restored. 
BLOWN FUSE IN POWER FEED DIS- 
CONNECT — Replace fuse. Restart is automatic. 
LOW WATER TEMPERATURE CUTOUT —
Press the control RESET button on control panel). 
Restart is automatic. 
AUXILIARY INTERLOCK — Automatic restart 
after condition is corrected. 
OPEN CONTROL CIRCUIT BREAKER — Close 
breaker. Unit will restart automatically. 
HIGH-PRESSURE SWITCH — Press unit 
START-STOP button to STOP then to START. 
Unit will restart under sequence control. 
LOW-PRESSURE SWITCH — Compressors will 
restart automatically when pressure comes up 
sufficiently. 
COMPRESSOR DISCHARGE TEMPERA-
TURE SENSOR — After discharge temperature 
cools down, press unit START-STOP button to 
STOP then to START. Unit will restart under 
sequence control. 
OIL SAFETY SWITCH — Press RESET button 
on the switch and press unit START-STOP button 
to STOP then to START. Unit will restart under 
sequence control. 
11