SAFETY CONSIDERATIONS 
Installation, start-up and servicing of this equip-
ment can be hazardous due to system pressures, 
electrical components and equipment location
. 
 
(roofs, elevated structures, etc.). 
Only trained, qualifal installers and service;,- 
mechanics should install, start-up and service ,thif 
equipment. 
When working on the equipment, observe pre-
cautions in the literature, tags, stickers and labels 
attached to the equipment and :to any other safety 
precautions 'that apply. 
• 
Follow all safety codes. 
• 
Wear safety glasses and work gloves. 
Carrier Parkway !
_S
yracuse, N.Y. 13221 
-Reciprocating 
uid Chillers 
For Model D Univ 
-. All 208/230 Volt Units Have EXte 
All Units Have Suction-Cutoff Unloading SysteM 
S070-160 
oltage Compressor Motors 
Floor must be strong engh,to support oper- 
ating weight (see Table 1). If necessary, add sup- 
mrting structure (steel beams or reinforced concrete 
to floor to transfer weight to nearest beams. 
Figure 1 shows location of 6 mounting holes. 
• 
Each point supports approximately 1/ 6 of the 
operating weight. 
Do not remove unit from skid until it is in final 
location. Rig from the 2-in. diam holes in the cooler 
end flanges. Lower carefully onto floor or rollers. 
Push or pull only on the skid, 
not the unit. 
If the 
unit is moved on rollers, use a minimum of 3, 
evenly spaced. 
Areas where corners will be located must be level 
*before unit is placed. Level unit with spirit level on 
frame channels. Bolt to floor (recommended for 
basement or ground floor installations that transmit 
vibration to ground without affecting building 
structure). 
All compressors have mufflers and are attached 
rigidly on top of rails mounted on spring vibration _ 
isolators. Remove rail mounting bolts so rails float_ 
freely on springs. 
If bolts are not removed, they 
may retighten from vibration during operation. 
Interconnecting piping must be flexible enough 
to prevent vibration transmission. If vibration still 
occurs, use isolators on unit. If installation is on 
upper
, 
floor where vibration cannot be transmitted 
to the ground, use field-purchased isolator springs 
under each unit mounting hole. 
• 
Use care in handling, rigging and setting bulky 
equipment. 
INSTALLATION 
LOCATION 
Do not store -u s in an area exposed to weather 
because of sensitive control mechanisms and elec-
trical ileviCes. Loate unit 'inders. 
See Fig. 1 for door' clearance. Allow following 
▪ 
clearances for service access. 
Front 
 3 to 4 ft 
Rear 
2 ft 
Ends  
tube removal at one (either) end, 
see Fig. 1; 2 ft at opposite end. 
Carrier Corporation 1981  
CONDENSER 
Run water supply lines as short as possible. Size 
lines according to head pressure available (not 
necessarily connection size), especially on cooling 
tower applications. See Carrier System Design 
Manual, Part 3, Piping Design: 
For installations requiring a water regulating 
valve, a separate valve is required (not supplied by 
Carrier) for each.circuit. Water bypass valves must 
be installed on cooling tower applications where 
low outdoor ambients affect head pressure. 
The 30HS units using air-cooled or evaporative 
condensers should have adequate means for head 
pressure control' when operating below 60 F out-
door ambient. 
Accessory water manifold packages are available 
to manifold 2 condensers on 30HR070-140 units. 
Connections are shown in Fig. 1. Each package 
Form 30HR.HS-22S1