EasyManua.ls Logo

Carrier 38AB - Pressure Differential

Carrier 38AB
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CONTROL
POWER
AT
38AD
UNIT
CR
Control
Relay
HD
Heating
Device
IFC
Indoor
Fan
Contactor
IFR
Indoor
Fan
Relay
LLS
Liquid
Line
Solenoid
R
Heating
Relay
(field-supplied
24-volt
sealed
coil,
10VA
maximum
rating)
SDR
Solenoid
Dropping
Relay
TB
Terminal
Board
TC
Thermostat,
Cooling
TH
Thermostat,
Heating
-—
Factory
Wiring
_Field
Wiring
^Jumper
removed
only
when
separate
24-volt
power
sources
are
available
for
heating
and
cooling
fTo
control
heating
device
and
provide
automatic
indoor
fan
operation
on
heating
->
Fig.
12
Control
Circuit
Wiring
with
24-Volt
Accessories
(38AD
units
only)
Preliminary
Charge
Refer
to
Carrier
Standard
Service
Techniques
Manual,
Chapter
1,
Section
1-8,
for
charging
methods
and
procedures
mentioned
below.
Charge
system
with
approximately
25
lb
of
R-22
(75
lb
for
38AD044,
38AB054,064
and
084
units)
by
the
Liquid
Charging
Method
and
Charging
by
Weight
Procedure.
Energize
the
Branch
Circuit,
set
space
thermostat
above
ambient.
Close
field
disconnect
switch
and
turn
on
unit
circuit
breakers.
Be
sure
compressor
crankcase
heater(s)
is
operating.
Allow
crankcase
heater(s)
to
operate
a
minimum
of
24
hours
before
starting
unit.
To
Start
Unit,
set
space
thermostat
below
ambient,
to
ensure
circuit
operation.
On
38AD044
and
38AB084,
push
control
circuit
reset
button(s).
After
starting
unit,
there
will
be
a
delay
of
about
'15
seconds
(12
seconds
on
38AD044
and
38AB084)
before
first
compressor
starts.
Charging
System
1.
Block
condenser
coils
to
maintain
125
F
con¬
densing
temp
at
280
psig,
then
add
additional
charge
to
clear
sight
glass.
(If
long
liquid
lines
or
vertical
lifts
greater
than
25
ft
are
used,
a
liquid
line
sight
glass
should
be
installed
at
condensing
unit
and
used
for
charging
purposes.)
2.
After
sight
glass
has
cleared,
additional
charge
must
be
added
per
Table
8,
to
flood
subcooler
circuits
in
condensers.
After
Charging
the
System,
allow
unit
to
run
for
about
20
minutes.
Stop
unit
and
check
compressor
oil
level.
Add
oil
only
if
necessary
to
bring
oil
into
view
in
sight
glass.
If
oil
is
added,
run
unit
for
additional
10
minutes.
Stop
unit
and
check
oil
level.
If
level
is
again
low,
add
oil
only
after
determining
that
piping
system
is
designed
for
proper
oil
return
and
that
the
system
is
not
leaking
oil.
Check
the
operation
of
all
safety
controls.
Replace
all
service
panels.
Be
sure
that
control
panel
door
is
closed
tightly.
Table
8
Charging
Data
(R-22)
UNIT
REFRIG
CHG
(lb)
REFRIG
STORAGE
CAP.
(lb)
f
Sub-cooler
Coil*
38AD024
8
70
38AD028
8
77
38AD034
7
99
3
8
AD
044
15
161
38AB054
12
154
38AB064
10
198
38AB084
21
322
*For
maximum
system
capacity
without
receiver
f
At
120
F
condensing
temp
with
condenser
80%
full
of
liquid
NOTE
Values
shown
do
not
include
charging
requirements
for
cooling
coils
and
piping
SERVICE
Capacity
Control
is
by
either
one
or
two
suction
pressure
actuated
unloaders.
Each
controls
two
cylinders.
Unloaders
are
factory
set
(see
Table
9)
but
may
be
field
adjusted.
No.
1
unloader
is
on
cylinder
bank
on
same
side
of
compressor
as
terminal
box.
CONTROL
SET
POINT
(cylinder
load
point)
is
adjustable
from
0
to
85
psig.
To
adjust,
turn
control
set
point
adjustment
nut
(Fig.
13)
clock¬
wise
to
its
bottom
stop.
In
this
position,
set
point
is
85
psig.
Then,
turn
adjustment
counterclockwise
to
desired
control
set
point.
Every
full
turn
counterclockwise
decreases
set
point
by
7.5
psig.
PRESSURE
DIFFERENTIAL
(difference
between
cylinder
load
and
unload
points)
is
adjustable
from
6
to
22
psig.
To
adjust,
turn
pressure
differential
adjustment
screw
(Fig.
13)
counterclockwise
to
its
back
stop
position.
In
this
position,
differential
is
6
psig.
Then,
turn
adjustment
clockwise
to
desired
pressure
differential.
Every
full
turn
clockwise
increases
differential
by
1.5
psig.
772
8

Related product manuals