EasyManua.ls Logo

Carrier 38AQS016 - Key System Features

Carrier 38AQS016
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
Table 1A — Physical Data — English
*Approximate charge with 25 ft of interconnecting piping. Use
appropriate charging charts for actual charging of unit.
†Refrigerant storage capacity at 120 F condensing temperature
with condenser 80% full of liquid.
**Head pressure control on cooling cycle only.
Table 1B — Physical Data — SI
*Approximate charge with 7.6 m of interconnecting piping. Use
appropriate charging charts for actual charging of unit.
†Refrigerant storage capacity at 48.9 C condensing temperature
with condenser 80% full of liquid.
**Head pressure control on cooling cycle only.
UNIT 38AQS 012 016
OPERATING WEIGHT (lb)
750 803
REFRIGERANT
Operating Charge (lb)*
R-22
30
R-22
37
COMPRESSOR
Recip Hermetic;
1460 Rpm (50 Hz)
1750 Rpm (60 Hz)
Model No.
Cylinders
Oil (pts)
Crankcase Heater (Watts)
06DF824
6
10
180
06DF537
6
10
180
OUTDOOR AIR FANS
Direct Drive — Axial Flow
Number
Speed (rpm)
50 Hz
60 Hz
Diameter (in.)
Motor Hp
Airflow (cfm)
50 Hz
60 Hz
kW (total)
50 Hz
60 Hz
2
900
1075
26
1
/
2
9210
11,000
1.05
1.46
2
900
1075
26
1
/
2
9210
11,000
1.05
1.46
OUTDOOR COIL
Plate Fins; 15 Per Inch
Rows Deep
Face Area (sq ft)
Storage Capacity (lb)†
2
29.2
27.2
3
29.2
40.1
CONTROLS
High-Pressure Switch (HPS)
Cutout (psig)
Cut-in (psig)
Loss-of-Charge Switch
(Liquid Line)
Cutout (psig)
Cut-in (psig)
Head Pressure
(No. 2 Fan Cycling)**
Opens (psig)
Closes (psig)
Oil Pressure Switch (Differential)
Set Point (psig)
(Close on Rise)
(Open on Fall)
Defrost Pressure Switch (HPS2)
Opens (psig)
Closes (psig)
400
300
7 ± 3
22 ± 5
160 ± 10
255 ± 10
9.5 ± 1
5
280 ± 10
180 ± 2
THERMOSTAT
Defrost Switch
Opens (F)
Closes (F)
65
27
80
27
UNIT 38AQS 012 016
OPERATING WEIGHT (kg)
340 364
REFRIGERANT
Operating Charge (kg)*
R-22
13.6
R-22
16.8
COMPRESSOR
Recip Hermetic;
24.3 r/s (50 Hz)
29.2 r/s (60 Hz)
Model No.
Cylinders
Oil (L)
Crankcase Heater (Watts)
06DF824
6
4.73
180
06DF537
6
4.73
180
OUTDOOR AIR FANS
Direct Drive — Axial Flow
Number
Speed (r/s)
50 Hz
60 Hz
Diameter (mm)
Motor kW
Airflow (L/s)
50 Hz
60 Hz
kW (total)
50 Hz
60 Hz
2
15
17.9
660
0.37
4350
5192
1.05
1.46
2
15
17.9
660
0.37
4350
5192
1.05
1.46
OUTDOOR COIL
Plate Fins; 590 Per Meter
Rows Deep
Face Area (sq m)
Storage Capacity (kg)†
2
2.71
12.3
3
2.71
18.2
CONTROLS
High-Pressure Switch (HPS)
Cutout (kPag)
Cut-in (kPag)
Loss-of-Charge Switch
(Liquid Line)
Cutout (kPag)
Cut-in (kPag)
Head Pressure
(No. 2 Fan Cycling)**
Opens (kPag)
Closes (kPag)
Oil Pressure Switch (Differential)
Set Point (kPag)
(Close on Rise)
(Open on Fall)
Defrost Pressure Switch (HPS2)
Opens (kPag)
Closes (kPag)
2758
2069
48 ± 20
152 ± 34
1103 ± 69
1758 ± 69
66 ± 7
34
1931 ± 69
1241 ± 14
THERMOSTAT
Defrost Switch
Opens (C)
Closes (C)
18.3
–2.8
26.7
–2.8