30
Heat pump heating performance continued
See notes on pg. 33.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES
°F
–3 7 17 2737475767
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
EDB CFM Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW†
38BYG042-30 Outdoor Section With F(A,B)4BN(F,B,C)048 Indoor Section
65
1275
1475
1675
19.7
20.0
20.4
18.1
18.4
18.7
2.77
2.82
2.88
23.5
23.8
24.1
21.6
21.9
22.2
2.88
2.92
2.98
27.5
27.9
28.3
25.1
25.4
25.8
3.00
3.03
3.07
31.9
32.4
32.7
28.4
28.7
29.1
3.13
3.15
3.18
36.9
37.4
37.8
33.6
34.0
34.4
3.28
3.29
3.31
43.0
43.5
44.0
43.0
43.5
44.0
3.48
3.47
3.49
50.4
51.1
51.6
50.4
51.1
51.6
3.75
3.73
3.75
58.0
58.8
59.2
58.0
58.8
59.2
4.08
4.05
4.01
70
1275
1475
1675
19.2
19.6
20.0
17.7
18.1
18.4
2.87
2.92
2.98
23.2
23.5
23.9
21.3
21.6
21.9
3.00
3.04
3.10
27.2
27.6
28.0
24.8
25.2
25.5
3.13
3.16
3.20
31.6
32.0
32.4
28.1
28.4
28.8
3.27
3.28
3.32
36.5
37.0
37.4
33.2
33.7
34.0
3.42
3.43
3.45
42.4
43.0
43.5
42.4
43.0
43.5
3.63
3.62
3.64
49.7
50.4
51.0
49.7
50.4
51.0
3.91
3.89
3.89
57.3
58.1
58.7
57.3
58.1
58.7
4.25
4.21
4.22
75
1275
1475
1675
18.7
19.1
19.5
17.2
17.6
18.0
2.97
3.03
3.09
22.9
23.2
23.6
21.0
21.4
21.7
3.12
3.17
3.22
26.9
27.3
27.6
24.5
24.9
25.2
3.26
3.29
3.33
31.3
31.7
32.1
27.8
28.1
28.5
3.41
3.42
3.46
36.1
36.6
37.0
32.9
33.3
33.7
3.58
3.58
3.60
41.9
42.5
43.0
41.9
42.5
43.0
3.79
3.78
3.79
49.0
49.7
50.3
49.0
49.7
50.3
4.08
4.05
4.05
56.5
57.3
57.9
56.5
57.3
57.9
4.42
4.38
4.38
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating
Indoor
Section Size
Heating
Capacity Power Capacity Power
CC5A/CD5AA 042 0.98 1.02 CK5A/CK5BT 048 0.98 0.96
CC5A/CD5AC 048 0.98 1.04
COILS + 58CV(A,X)110-22 VARIABLE-SPEED FURNACE
CC5A/CD5AW 048 0.99 1.01 CC5A/CD5AC 048 0.98 1.03
CD5AA 048 0.99 1.01 CC5A/CD5AW 048 0.98 0.98
CE3AA 042 0.99 1.01 CD5AA 048 0.98 0.98
048 0.99 1.00 CE3AA 048 0.98 0.97
CF5AA 048 0.98 1.01 CK3BA 048 0.98 0.95
CK3BA 042 0.98 1.00 CK5A/CK5BA 048 0.98 0.95
048 0.99 1.00 CK5A/CK5BT 048 0.98 0.95
CK5A/CK5BA 042 0.98 1.00 CK5A/CK5BW 048 0.98 0.95
048 0.99 0.99
COILS + 58CV(A,X)135-22 VARIABLE-SPEED FURNACE
CK5A/CK5BE 042 0.95 0.96 CC5A/CD5AC 048 0.98 1.03
CK5A/CK5BT 042 0.98 1.00 CC5A/CD5AW 048 0.98 0.98
048 0.99 0.99 CD5AA 048 0.98 0.98
CK5A/CK5BW 048 0.99 1.00 CE3AA 048 0.98 0.97
F(A,B)4BN(F,B,C) 042 0.99 0.99 CK3BA 048 0.98 0.95
042 0.99 1.03 CK5A/CK5BA 048 0.98 0.95
048 1.00 1.00 CK5A/CK5BT 048 0.98 0.95
FC4CN(F,B) 042 0.99 1.03 CK5A/CK5BW 048 0.98 0.95
048 1.00 1.00
COILS + 58CV(A,X)155-22 VARIABLE-SPEED FURNACE
FG3AAA 048 0.99 0.99 CC5A/CD5AC 048 0.98 1.03
FK4DNB 006 0.98 0.88 CC5A/CD5AW 048 0.98 0.98
FK4DNF 003 0.97 0.98 CD5AA 048 0.98 0.98
005 0.98 0.91 CE3AA 048 0.98 0.97
COILS + 58CV(A,X)090-16 VARIABLE-SPEED FURNACE CK3BA 048 0.98 0.95
CC5A/CD5AC 048 0.98 1.04 CK5A/CK5BA 048 0.98 0.95
CD5AA 048 0.98 0.98 CK5A/CK5BT 048 0.98 0.95
CE3AA 048 0.98 0.97 CK5A/CK5BW 048 0.98 0.95
CK3BA 048 0.98 0.96
COILS + 58MVP080-14 VARIABLE-SPEED FURNACE
CK5A/CK5BA 048 0.98 0.96 CD5AA 048 0.98 0.98
—— CE3AA 048 0.98 0.98