38MAR-04SI                                                                            Specifications subject to change without notice.                                                                     19
Ductless Start-Up Checklist (CONT)
Piping
Leak Check: 
System held 500 psig (max. 550psi) for a minimum of 30 minutes using dry nitrogen.    YES:______ NO:______
Evacuation Method: 
•
Was the Triple Evacuation Method used as outlined in the installation manual?      YES:______ NO:______
• Was the Deep Vacuum Method used as outlined in the installation manual?             YES:______ NO:_______
• Did the System Hold 500 microns for 1 hour?                   YES:______ NO:_______
• Does the line set match the diameter of the evaporator connections?                    YES:______ NO:_______
• For Conventional Fan Coils, does the line set match the outdoor unit size?           YES:______ NO:_______
Single Zone Piping:
Has the liquid pipe length been measured and the additional charge calculated?    Size:___________ Length:_________ Charge:____________
Performance Check
Error Codes
Were there any error codes present at start-up?         YES:______ NO:______
Comments:
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
NOTES:
PORT LIQUID SIZE SUCTION SIZE LENGTH CHARGE
NOTES:____________________________________
___________________________________________
___________________________________________
A
For 1:1 Single Zone Systems: Adjust the set-point to create an operational call for the desired testing operation. Allow the system to run for a 
minimum of 10 min. and record the following details:
(Operational data recorded on applicable heads with the wireless remote controller’s Point Check function)
UNIT
SET-POINT
MODE T1 T2 T3 T4 Tb Tp Th LA/Lr
A
Indoor Unit Error Code: Notes:
Outdoor Unit Error Code:
Wall Controller:
24V Interface: