3
Table 2 — 38VMH Physical Data
* The source voltage must not fluctuate more than ± 10%.
Rated conditions:
Cooling: Indoor air temperature 80°F dry bulb / 67°F wet bulb,
Outdoor air temperature 95°F dry bulb
Heating: Indoor air temperature 70°F dry bulb,
Outdoor air temperature 47°F dry bulb / 43°F wet bulb
** The amount does not consider extra piping length. Refrigerant
must be added on site in accordance with the actual piping
length.
†† In case the diversity exceeds 135%, the type of indoor unit is
limited and the maximum number of indoor unit is reduced.
*** These values, measured in anechoic chamber at a point 1 m in
front of the unit at a height of 1.4 m. During actual operation,
these values are normally somewhat higher as a result of
ambient conditions.
****Unit may operate in Heating mode in outdoor ambient temperatures
down to -13°F wb as long as unit was started when ambient
temperature was 5°F wb or warmer.
UNIT 036 048 060
NOMINAL TONS (Ton) 3 4 5
POWER SUPPLY (V-Ph-Hz)* 208/230-1-60
COOLING CAPACITY WITH NON-DUCTED & DUCTED INDOOR UNITS†
Nominal (kBtu/h) 36 48 60
Rated (kBtu/h) 36 48 60
HEATING CAPACITY WITH NON-DUCTED & DUCTED INDOOR UNITS†
Nominal (kBtu/h) 40 52.5 66
Rated (kBtu/h) 40 52.5 66
ELECTRICAL CHARACTERISTICS WITH NON-DUCTED INDOOR UNITS
Cooling
Power Consumption (kW) 3.10 4.60 6.10
EER (Btu/Wh) 12.10 11.00 9.50
SEER (Btu/Wh) 19.20 19.20 18.60
Heating
Power Consumption (kW) 3.10 4.30 5.80
COP (W/W) 3.62 3.42 3.19
HSPF (Btu/Wh) 9.20 9.20 10.00
ELECTRICAL CHARACTERISTICS WITH DUCTED INDOOR UNITS
Cooling
Power Consumption (kW) 2.90 4.70 6.10
EER (Btu/Wh) 11.90 9.80 9.30
SEER (Btu/Wh) 17.80 17.80 18.20
Heating
Power Consumption (kW) 3.00 4.20 5.70
COP (W/W) 3.68 3.54 3.26
HSPF (Btu/Wh) 9.60 9.60 10.00
UNIT DIMENSIONS (W x H x D) (in.) 35
1
/
2
x 52
1
/
4
x 15
3
/
4
UNIT NET WEIGHT (lb) 220
COMPRESSOR TYPE Hermetic Rotary DC Inverter Compressor
FAN UNIT
Air Volume (cfm) 4100
Motor Output (W) 90+90
REFRIGERANT SHIPPING CHARGE (lb)** 8.6
REFRIGERANT CONNECTING PORT DIAMETER
Suction Side (in.)
5
/
8
3
/
4
Liquid Side (in.)
3
/
8
OPERATION TEMPERATURE RANGE
Cooling (F db) 5~118
Heating (F wb)**** -13~64
MAX NUMBER OF CONNECTED INDOOR
UNITS
5 7 9
MAXIMUM CAPACITY OF COMBINED INDOOR
UNITS ††
50%~130%
SOUND PRESSURE LEVEL (db(A))*** 58.7 60.1 60.7
LEGEND
COP Coefficient of Performance
db Dry Bulb
EER Energy Efficiency Ratio
ESP External Static Pressure
wb Wet Bulb

Related product manuals