24
- The clearance between the units must be sufficient to
ensure that the discharge air from one unit does not mix
with the supply air of another unit.
38XTZ 014
Fig. 24
- If the air enters through the units on one side only and is
discharged through the top, the clearances can be reduced.
38XTZ 011, 016, 020 and 024
Fig. 25
- The air enters through three sides and is discharged
through the top.
Table 8 - Minimum clearances between units (mm)
38XTZ A B C
007 and 008 200 500 400
014 500 700 500
011, 016, 020 and 024 500 700 500
Concrete base
Concrete base
Installation on the ground
- 38XTZ units can be positioned on the floor of a patio, on
the ground or on a lawn. If installed on the ground or on
the lawn they should be mounted on a 100 mm high
concrete base that is 100 mm larger than the base unit on
all four sides.
38XTZ 007 and 008
Fig. 26
38XTZ 011 to 024
Fig. 27
- If this type of installation is used, ensure that the units are
not affected by flooding, snow accumulation or leaves.
- Ensure that the units are secured to prevent injuries to
people handling or working on the units.
IMPORTANT: Rainwater is drained through the unit base.
For this reason the units must be elevated above the concrete
base to allow correct drainage.
- Rainwater drainage
38XTZ units incorporate drillholes in the base in order to
correctly drain any condensate or rainwater which may
enter the unit in the fan area. Ensure correct drainage.