EasyManua.ls Logo

Carrier 38YXA - Refrigerant System Preparation; Install Adapter Tube

Carrier 38YXA
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Data
UNIT
SIZE-SERIES
V/PH
OPER VOLTS* COMPRESSOR
FAN
FLA
MCA
60°C
MIN
WIRE
SIZE†
75°C
MIN
WIRE
SIZE†
60°C
MAX
LENGTH
(FT)‡
75°C
MAX
LENGTH
(FT)‡
MAX FUSE**
OR
CKT BKR
AMPS
Max Min LRA RLA
024-30
208/230/1 253 187
61.0 15.1 0.8 19.7 14 14 39 37 30
030-30 72.5 14.7 1.1 19.5 14 14 39 37 30
036-30 83.0 15.4 1.1 20.4 12 12 60 57 30
042-30 104.0 21.1 1.1 27.5 10 10 71 68 40
048-30 109.0 20.5 1.4 27.0 10 10 74 70 40
060-31 158.0 27.6 1.4 35.9 8 8 86 82 60
* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
If other than uncoated (non-plated), 60° or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG)
is used, consult applicable tables of the NEC (ANSI/NFPA 70).
If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM), trade name
ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-30.
Length shown is as measured 1 way along the wire path between the unit and the service panel for a voltage drop not to exceed 2 percent.
** Time-delay fuse.
FLA—Full Load Amps
LRA—Locked Rotor Amps
MCA—Minimum Circuit Amp
RLA—Rated Load Amps
NOTE: 1. Control circuit is 24v on all units and requires external power source.
2. Copper wire must be used from service disconnect to unit.
3. All motors/compressors contain internal overload protection.
Tested Combination Ratings*
UNIT SIZE-
SERIES
INDOOR
UNIT
ARI STANDARD RATINGS†
Cooling Heating
TC
SEER
EER
High-Temp Low-Temp
HSPF
Factory-
Supplied
Enhance-
ment
Standard
Rating
Carrier
Gas
Furnace
or
Accessory
TDR‡
Accessory
TXV**
TC COP TC COP
024-30 FX4ANF030 25,000 TDR & TXV 13.00 11.50 25,000 3.30 16,600 2.30 8.00
030-30 FX4ANF030 29,000 TDR & TXV 13.00 11.40 30,000 3.50 18,500 2.34 8.00
036-30 FX4ANF042 35,000 TDR & TXV 13.00 11.30 35,000 3.35 21,600 2.34 7.70
042-30 FV4ANF003 40,500 TDR & TXV 13.10 11.30 40,500 3.35 25,400 2.45 7.70
048-30 FV4ANF005 45,500 TDR & TXV 13.50 12.00 47,500 3.50 28,300 2.50 8.50
060-31 FV4ANB006 58,500 TDR & TXV 13.20 11.00 60,000 3.50 37,000 2.53 8.00
* Outdoor section/indoor section combination tested in accordance with DOE test procedure for heat pumps.
Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit.
High-Temp Heating Standard: 70°F (21°C) db indoor entering air temperature and 47°F (8°C) db 43°F (6°C) wb air entering outdoor unit.
Low-Temp Heating Standard: 70°F (21°C) db indoor entering air temperature and 17°F (-9°C) db 15°F (-10°C) wb air entering outdoor unit.
In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance. Use either
the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. All Carrier furnaces are equipped with TDR except for the 58GFA.
** Based on computer simulation. TXV must be R-410A compatible and hard shutoff type.
COP—Coefficient of Performance
EER—Energy Efficiency Ratio
HSPF—Heating Seasonal Performance Factor
SEER—Seasonal Energy Efficiency Ratio
TC—Total Capacity (Btuh)
TDR—Time-Delay Relay
TXV—Thermostatic Expansion Valve
Sound Rating (dBA)
UNIT SIZE-SERIES SOUND RATING
024-30 70
030-30 72
036-30 74
042-30 73
048-30 76
060-31 76
4

Other manuals for Carrier 38YXA

Related product manuals