WIRING
The indoor and outdoor units have their own power supply (single point connection on units with electric heat). Low voltage wires run
between the indoor and outdoor units. Two wires are required for cooling only systems and seven wires are required for heat pumps.
ELECTRICAL DATA
38HDF/38QRF ELECTRICAL DATA
38HDF/38QRF
UNIT SIZE
V --- P H --- H z
VOLTAGE RANGE*
COMPRESSOR OUTDOOR FAN MOTOR
MIN CKT
AMPS
FUSE/
CKT
BKR
AMPS
RLA LRA FLA NEC Hp kW Out
Min Max
018 208/230---1 ---60 187 253 9.0 48.0 0.80 0.125 0.09 12.1 20
024 208/230---1 ---60 187 253 12.8 58.3 0.80 0.125 0.09 16.8 25
38QRF030 208/230 ---1---60 187 253 14.1 73.0 1.50 0.25 0.19 18.4 30
38HDF030 208/230---1 ---60 187 253 14.1 73.0 0.80 0.125 0.09 18.4 30
035
208/230---1 ---60 187 253 16.7 79.0 1.50 0.25 0.19 22.3 35
208/230---3 ---60 187 253 10.4 73.0 1.50 0.25 0.19 14.5 20
4 60 --- 3 --- 6 0 414 506 5.8 38.0 0.80 0.25 0.19 8.7 15
036
208/230---1 ---60 187 253 17.9 112.0 1.45 0.25 0.19 23.8 40
208/230---3 ---60 187 253 13.2 88.0 1.45 0.25 0.19 18.0 30
4 60 --- 3 --- 6 0 414 506 6.0 44.0 0.80 0.25 0.19 8.3 15
40KMC FAN COIL ELECTRICAL DATA
40KMC
Unit Size
V --- P H --- H z
Voltage Range FAN
Condensate
Pump FLA
Louver
Motor
FLA
Power
Min. Max FLA Watts
MIN CKT
AMPS
FUSE/
CKT
BKR
AMPS
018 208/230 ---1---60 187 253 0.55 120 0.06 0.01 0.8 15
024 208/230 ---1---60 187 253 0.50 110 0.06 0.01 0.7 15
030 208/230 ---1---60 187 253 0.95 210 0.06 0.01 1.3 15
036 208/230 ---1---60 187 253 0.95 210 0.06 0.01 1.3 15
40KMQ FAN COIL ELECTRICAL DATA
40KMQ
Unit Size
V --- P H --- H z
Voltage
Range
FAN
Condensate
Pump FLA
Louver
Motor
FLA
Electric
Heaters
Power
Min. Max FLA
Motor
Power
(Watts)
kW FLA
MIN
CKT
AMPS
FUSE/
CKT
BKR
AMPS
018 208/ 230 ---1 ---60 187 253 0.50 110 0.06 0.01 3 12.5 16.3 20
024 208/ 230 ---1 ---60 187 253 0.50 110 0.06 0.01 3 12.5 16.3 20
030 208/ 230 ---1 ---60 187 253 0.95 210 0.06 0.01 3 12.5 16.9 20
036 208/ 230 ---1 ---60 187 253 0.95 210 0.06 0.01 3 12.5 16.9 20
*Permissible limits of the voltage range at which unit will operate satisfactorily.
LEGEND
FLA --- F u l l L o a d A mp s
MCA --- Minimum Circuit Amps per NEC Section 430---24
NEC --- National Electrical Code
RLA --- RatedLoadAmps(Compressor)
NOTES:
1. In compliance with NEC requirements for multi---motor and combination
load equipment (r e f er to NE C Articles 430 and 440), the over ---current
protective device for the unit shall be fuse or equipped with a breaker.
2. Motor RLA valu es ar e established in accordance with UL (Underwriters
Laboratories) Standar d 465.
®
4QKMC, KMQ / 38HDF, QRF