13
PERFORMANCE DATA (CONT.)
COOLING CAPACITIES
COOLING ONLY 38HDF024 WITH 40KMC024
Tem p ° F (° C)
Air Entering
Condenser
(Edb)
Air Entering Evaporator --- Cfm/BF
445 / 0.05 530 / 0.05 680 / 0.05
Air Entering Evaporator --- Ewb ° F (° C)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
55
(12.8)
TCG 21.7 23.5 25.0 27.3 22.9 24.5 26.7 28.2 24.7 26.6 28.4 29.2
SHG 20.1 17.8 15.5 13.7 21.3 18.8 16.7 14.4 23.9 21.5 18.4 15.2
TC 21.5 23.2 24.8 27.1 22.6 24.1 26.4 27.9 24.3 26.2 28.0 28.8
kW 1.22 1.23 1.23 1.24 1.23 1.23 1.23 1.21 1.22 1.24 1.24 1.21
CMP 1.01 1.02 1.02 1.03 1.00 1.00 1.00 0.98 0.96 0.98 0.98 0.95
LDB 39.2 44.2 49.3 53.5 43.7 48.4 52.2 56.6 48.3 51.8 56.4 60.8
LWB 36.5 42.0 47.9 53.4 39.3 45.0 50.3 56.3 42.6 48.0 53.6 59.9
65
(18.3)
TCG 20.9 22.8 24.7 26.4 22.3 24.1 25.8 28.2 23.7 25.4 27.8 29.2
SHG 19.6 17.6 15.5 13.0 21.1 19.2 16.2 14.3 23.7 21.0 18.1 14.7
TC 20.6 22.6 24.5 26.1 22.0 23.8 25.4 27.9 23.3 25.0 27.4 28.7
kW 1.36 1.38 1.40 1.41 1.38 1.39 1.40 1.40 1.39 1.40 1.41 1.41
CMP 1.15 1.17 1.19 1.20 1.15 1.16 1.17 1.17 1.13 1.14 1.15 1.15
LDB 40.2 44.6 49.4 54.7 44.1 47.7 53.1 56.8 48.6 52.6 56.6 61.5
LWB 37.4 42.6 48.2 54.2 39.8 45.2 51.0 56.3 43.2 48.7 54.0 59.9
75
(23.9)
TCG 20.1 22.0 24.1 25.9 21.7 23.3 25.1 27.5 23.0 24.7 26.8 28.6
SHG 19.1 17.4 15.3 12.9 20.5 19.0 16.1 13.7 23.0 21.1 17.9 14.7
TC 19.9 21.8 23.8 25.6 21.4 23.0 24.8 27.2 22.6 24.3 26.4 28.2
kW 1.53 1.55 1.57 1.58 1.54 1.56 1.57 1.58 1.56 1.57 1.58 1.58
CMP 1.32 1.34 1.36 1.37 1.31 1.33 1.34 1.35 1.30 1.31 1.32 1.32
LDB 41.2 45.1 49.8 55.0 45.1 48.1 53.4 57.7 49.5 52.4 57.0 61.6
LWB 38.3 43.4 48.8 54.6 40.4 45.9 51.5 56.8 43.7 49.1 54.5 60.2
85
(29.4)
TCG 19.4 21.2 23.2 25.0 20.5 22.3 24.2 26.7 22.4 23.8 25.8 27.8
SHG 18.6 17.0 14.9 12.5 20.5 18.6 15.8 13.4 22.4 20.9 17.6 14.5
TC 19.1 20.9 23.0 24.8 20.1 22.0 23.9 26.4 21.9 23.3 25.4 27.3
kW 1.71 1.73 1.76 1.76 1.72 1.75 1.76 1.77 1.75 1.76 1.77 1.78
CMP 1.50 1.52 1.55 1.55 1.49 1.52 1.53 1.54 1.49 1.50 1.51 1.52
LDB 42.3 45.9 50.6 55.7 45.2 48.7 53.7 58.2 50.4 52.6 57.3 61.8
LWB 39.1 44.3 49.6 55.3 41.5 46.7 52.2 57.4 44.1 49.7 55.0 60.6
95
(35.0)
TCG 18.3 20.2 22.2 24.1 19.7 21.3 23.1 25.6 21.5 22.7 24.0 26.6
SHG 18.3 16.5 14.4 12.1 19.7 18.2 15.4 13.0 21.5 20.7 16.7 14.1
TC 18.0 19.9 22.0 23.8 19.4 21.0 22.8 25.3 21.1 22.3 23.6 26.1
kW 1.90 1.93 1.96 1.97 1.92 1.94 1.97 1.97 1.95 1.96 2.05 2.06
CMP 1.69 1.72 1.75 1.76 1.69 1.71 1.74 1.74 1.69 1.70 1.79 1.80
LDB 42.8 46.8 51.5 56.5 46.5 49.3 54.6 58.9 51.6 52.9 58.0 62.3
LWB 40.3 45.3 50.4 56.0 42.2 47.5 52.9 58.1 44.7 50.3 55.7 61.1
105
(40.6)
TCG 17.5 19.1 21.1 23.0 18.8 20.1 22.0 24.3 20.6 21.4 23.2 25.3
SHG 17.5 16.0 13.9 11.7 18.8 17.7 15.0 12.5 20.6 20.0 16.5 13.6
TC 17.2 18.9 20.9 22.8 18.5 19.8 21.7 24.0 20.2 21.0 22.8 24.8
kW 2.11 2.14 2.18 2.19 2.13 2.15 2.19 2.19 2.16 2.18 2.19 2.20
CMP 1.90 1.93 1.97 1.98 1.90 1.92 1.96 1.96 1.90 1.92 1.93 1.94
LDB 44.5 47.8 52.5 57.4 48.1 50.2 55.2 59.8 52.8 53.8 58.8 62.9
LWB 41.1 46.3 51.4 56.9 42.9 48.5 53.7 58.9 45.3 51.0 56.4 61.7
115
(46.1)
TCG 16.6 17.8 19.9 21.8 17.8 18.7 20.7 22.9 19.5 20.3 21.7 23.8
SHG 16.6 15.5 13.3 11.1 17.8 17.1 14.5 11.9 19.5 19.0 16.1 12.9
TC 16.3 17.6 19.6 21.5 17.5 18.4 20.4 22.5 19.1 19.8 21.2 23.3
kW 2.33 2.36 2.41 2.42 2.36 2.38 2.42 2.43 2.40 2.41 2.42 2.43
CMP 2.12 2.15 2.20 2.21 2.13 2.15 2.19 2.20 2.14 2.15 2.16 2.17
LDB 46.4 49.0 53.6 58.5 49.8 51.1 56.0 60.7 54.2 55.2 59.3 63.8
LWB 42.1 47.6 52.5 57.9 43.8 49.5 54.6 59.8 46.0 51.7 57.2 62.4
125
(51.7)
TCG 15.5 16.3 18.4 20.3 16.7 17.2 19.2 21.2 18.3 18.3 20.1 22.1
SHG 15.5 14.9 12.7 10.5 16.7 16.4 13.9 11.3 18.3 18.3 15.5 12.2
TC 15.2 16.1 18.1 20.0 16.4 16.9 18.9 20.9 17.9 17.9 19.6 21.6
kW 2.57 2.60 2.65 2.67 2.60 2.61 2.66 2.67 2.64 2.64 2.67 2.67
CMP 2.36 2.39 2.44 2.46 2.37 2.38 2.43 2.44 2.38 2.38 2.41 2.41
LDB 48.6 50.1 54.9 59.6 51.6 52.4 57.0 61.8 55.9 56.0 60.0 64.7
LWB 43.2 48.9 53.8 59.0 44.7 50.6 55.6 60.8 46.7 52.4 58.0 63.2
Rating condition
LEGEND
BF --- Bypass Factor
CMP --- Compressor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
k W --- To ta l Po we r
LDB --- Leaving Dry Bulb
L W B --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Ca pacity (1000 Btu/hour)
TC --- Total Net Cool ing Capacity (1000 Btu/hour)
---
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. Th e SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from
SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
0KMC, KMQ / 38HDF, QR