EasyManua.ls Logo

Carrier 40KMQ - Page 22

Carrier 40KMQ
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
PERFORMANCE DATA (CONT.)
COOLING CAPACITIES
HEAT PUMP 38QRF030 WITH 40KMQ03036
Tem p ° F (° C)
Air Entering
Condenser
(Edb)
Air Entering Evaporator --- Cfm/BF
635 / 0.05 720/0.05 875/0.05
Air Entering Evaporator --- Ewb ° F (° C)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
55
(12.8)
TCG 27.9 30.4 32.9 35.0 29.2 31.4 33.8 35.8 31.0 32.8 34.9 36.6
SHG 26.6 24.1 20.9 17.5 27.6 25.6 21.9 18.2 31.0 28.1 23.4 19.1
TC 27.4 29.9 32.4 34.5 28.6 30.8 33.2 35.2 30.3 32.0 34.1 35.9
kW 1.63 1.63 1.64 1.65 1.63 1.64 1.65 1.65 1.64 1.64 1.65 1.65
CMP 1.20 1.21 1.22 1.23 1.17 1.18 1.19 1.19 1.14 1.14 1.15 1.15
LDB 42.4 46.2 51.2 56.5 45.6 48.4 53.4 58.5 48.3 51.6 56.8 61.5
LWB 39.0 44.3 49.8 55.8 40.7 46.2 51.7 57.7 43.1 48.8 54.4 60.3
65
(18.3)
TCG 27.3 29.5 32.2 34.7 28.3 30.5 33.2 35.5 30.4 31.9 34.4 36.3
SHG 26.0 23.8 20.7 17.3 28.3 25.4 21.8 18.0 30.4 28.1 23.6 18.9
TC 26.8 29.0 31.7 34.2 27.7 29.9 32.6 34.9 29.7 31.2 33.6 35.6
kW 1.81 1.82 1.82 1.84 1.81 1.82 1.83 1.84 1.82 1.82 1.83 1.84
CMP 1.39 1.39 1.40 1.41 1.35 1.36 1.37 1.38 1.32 1.32 1.33 1.34
LDB 43.2 46.7 51.5 56.6 44.7 48.7 53.6 58.7 48.9 51.6 56.6 61.7
LWB 39.5 44.9 50.3 55.9 41.2 46.7 52.1 57.8 43.4 49.1 54.6 60.4
75
(23.9)
TCG 26.2 28.6 31.1 34.0 27.6 29.3 32.1 34.8 29.6 30.7 33.5 35.9
SHG 26.2 23.2 20.2 17.1 27.6 24.9 21.5 17.8 29.6 27.6 23.4 18.9
TC 25.7 28.1 30.6 33.5 26.9 28.7 31.5 34.2 28.8 29.9 32.7 35.1
kW 2.01 2.02 2.03 2.04 2.02 2.02 2.03 2.04 2.02 2.03 2.04 2.05
CMP 1.59 1.60 1.60 1.61 1.56 1.56 1.57 1.58 1.52 1.53 1.54 1.55
LDB 43.0 47.6 52.2 57.0 45.7 49.3 54.0 59.0 49.8 52.1 56.7 61.7
LWB 40.3 45.6 50.9 56.3 41.7 47.4 52.6 58.1 43.8 49.7 55.0 60.6
85
(29.4)
TCG 25.1 27.1 29.8 32.8 26.5 28.0 30.8 33.7 28.5 29.3 32.1 34.9
SHG 25.1 22.9 19.7 16.6 26.5 24.6 21.0 17.4 28.5 27.0 23.0 18.7
TC 24.6 26.6 29.3 32.3 25.9 27.4 30.2 33.1 27.8 28.5 31.3 34.1
kW 2.24 2.25 2.26 2.27 2.24 2.25 2.26 2.27 2.25 2.25 2.26 2.28
CMP 1.81 1.82 1.83 1.85 1.78 1.79 1.80 1.81 1.75 1.75 1.76 1.78
LDB 44.4 47.9 52.9 57.7 47.1 49.7 54.6 59.5 50.9 52.7 57.2 62.0
LWB 41.1 46.6 51.7 57.0 42.4 48.2 53.3 58.7 44.3 50.4 55.6 60.9
95
(35.0)
TCG 24.0 25.5 28.3 31.3 25.3 26.4 29.2 32.2 27.2 27.8 30.0 33.3
SHG 24.0 22.2 19.2 16.0 25.3 23.8 20.4 16.8 27.2 26.4 21.8 18.1
TC 23.5 25.0 27.8 30.8 24.7 25.8 28.6 31.6 26.5 27.0 29.2 32.6
kW 2.47 2.49 2.51 2.52 2.49 2.49 2.51 2.53 2.50 2.50 2.65 2.66
CMP 2.04 2.06 2.08 2.10 2.03 2.03 2.05 2.07 2.00 2.00 2.15 2.16
LDB 46.1 48.9 53.6 58.5 48.6 50.6 55.4 60.1 52.3 53.3 57.8 62.5
LWB 41.9 47.6 52.6 57.8 43.2 49.1 54.1 59.3 45.0 51.0 56.3 61.5
105
(40.6)
TCG 22.7 23.8 26.6 29.5 24.0 24.7 27.4 30.5 25.8 26.3 28.6 31.6
SHG 22.7 21.4 18.4 15.3 24.0 23.0 19.7 16.2 25.8 24.9 21.8 17.6
TC 22.2 23.3 26.1 29.1 23.4 24.0 26.8 29.9 25.0 25.6 27.8 30.8
kW 2.72 2.73 2.77 2.79 2.73 2.75 2.78 2.80 2.76 2.77 2.79 2.81
CMP 2.29 2.31 2.35 2.37 2.27 2.29 2.32 2.34 2.26 2.27 2.29 2.31
LDB 47.9 50.0 54.6 59.5 50.3 51.6 56.2 61.0 53.8 54.8 58.4 63.0
LWB 42.9 48.7 53.6 58.7 44.0 50.0 55.1 60.1 45.7 51.7 57.0 62.1
115
(46.1)
TCG 21.3 22.0 24.6 27.6 22.5 22.9 25.4 28.4 24.2 24.2 26.4 29.4
SHG 21.3 20.5 17.6 14.6 22.5 21.9 18.9 15.5 24.2 24.2 21.0 16.8
TC 20.8 21.5 24.1 27.1 21.9 22.3 24.8 27.8 23.5 23.5 25.7 28.7
kW 2.99 3.00 3.05 3.09 3.01 3.01 3.06 3.10 3.03 3.03 3.07 3.10
CMP 2.56 2.57 2.62 2.66 2.55 2.55 2.60 2.64 2.53 2.53 2.57 2.60
LDB 49.9 51.2 55.7 60.4 52.1 53.1 57.2 61.8 55.4 55.5 59.2 63.8
LWB 43.9 49.9 54.8 59.7 44.9 51.0 56.1 61.0 46.5 52.6 57.8 62.9
125
(51.7)
TCG 19.8 20.2 22.4 25.4 20.9 20.9 23.1 26.1 22.5 22.5 24.1 27.1
SHG 19.8 19.3 16.8 13.8 20.9 20.9 18.0 14.6 22.5 22.5 20.1 16.0
TC 19.3 19.7 21.9 24.9 20.3 20.3 22.5 25.5 21.7 21.7 23.3 26.3
kW 3.28 3.29 3.33 3.40 3.30 3.30 3.35 3.41 3.33 3.33 3.37 3.42
CMP 2.85 2.86 2.91 2.97 2.84 2.84 2.89 2.95 2.83 2.83 2.87 2.92
LDB 52.1 53.0 57.0 61.5 54.2 54.3 58.2 62.8 57.3 57.3 60.1 64.6
LWB 44.9 51.0 56.0 60.9 45.9 52.1 57.2 62.1 47.4 53.4 58.7 63.7
Rating condition
Not recommended for long---term operation.
LEGEND
BF --- Bypass Factor
CMP --- Compressor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
k W --- To ta l Po we r
LDB --- Leaving Dry Bulb
L W B --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Ca pacity (1000 Btu/hour)
TC --- Total Net Cool ing Capacity (1000 Btu/hour )
TCG --- Gross C ooling C a pacity (1000 Btu/hour)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. Th e SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
4
0KMC, KMQ / 38HDF, QR
F

Other manuals for Carrier 40KMQ

Related product manuals