24
PERFORMANCE DATA (CONT.)
INSTANTANEOUS AND INTEGRATED HEATING RATINGS
40KMQ01824 WITH 38QRF018
Air Temperature
Entering Indoor
Unit ° F C)
Indoor
Airflow
(CFM)
L --- M --- H
Item
Air Temperature Entering Outdoor Coil ° F C)
17 ( --- 8.3) 27 ( --- 2.8) 37 (2.8) 47 (8.3) 57 (13.9)
Instant.
Rating
Integrated
Rating
Instant.
Rating
Integrated
Rating
Instant.
Rating
Integrated
Rating
Instant.
Rating
Integrated
Rating
Instant.
Rating
Integrated
Rating
55 (12.8)
470
Cap 10.64 9.70 12.67 11.25 14.73 13.41 16.75 16.75 19.45 19.45
kW 1.07 1.12 1.20 1.33 1.39
560
Cap 10.82 9.87 12.87 11.43 14.85 13.52 17.07 17.07 19.86 19.86
kW 1.06 1.10 1.20 1.27 1.32
695
Cap 11.02 10.05 13.10 11.63 15.04 13.69 17.47 17.47 20.31 20.31
kW 1.05 1.08 1.18 1.20 1.27
60 (15.6)
470
Cap 10.31 9.40 12.41 11.02 14.48 13.17 16.61 16.61 19.10 19.10
kW 1.12 1.17 1.25 1.36 1.46
560
Cap 10.52 9.59 12.59 11.18 14.75 13.42 16.86 16.86 19.54 19.54
kW 1.11 1.16 1.22 1.32 1.39
695
Cap 10.72 9.77 12.82 11.38 14.92 13.58 17.16 17.16 20.00 20.00
kW 1.10 1.14 1.21 1.28 1.33
65 (18.3)
470
Cap 9.96 9.08 12.08 10.73 14.31 13.02 16.42 16.42 18.76 18.76
kW 1.17 1.23 1.29 1.40 1.52
560
Cap 10.08 9.19 12.27 10.89 14.57 13.26 16.56 16.56 19.18 19.18
kW 1.16 1.22 1.25 1.39 1.45
695
Cap 10.39 9.47 12.51 11.11 14.80 13.47 16.89 16.89 19.65 19.65
kW 1.16 1.20 1.24 1.34 1.39
70 (21.1)
470
Cap 9.49 8.66 11.74 10.43 13.99 12.74 16.26 16.26 18.43 18.43
kW 1.28 1.28 1.35 1.46 1.59
560
Cap 9.75 8.89 11.99 10.65 14.24 12.96 16.43 16.43 18.84 18.84
kW 1.27 1.26 1.32 1.45 1.51
695
Cap 9.50 8.66 12.25 10.88 14.54 13.23 16.80 16.80 19.31 19.31
kW 1.26 1.27 1.29 1.44 1.46
75 (23.9)
470
Cap 9.23 8.42 11.33 10.06 13.63 12.41 15.90 15.90 18.11 18.11
kW 1.28 1.35 1.41 1.49 1.65
560
Cap 9.37 8.54 11.63 10.33 13.90 12.65 16.23 16.23 18.50 18.50
kW 1.28 1.32 1.38 1.46 1.59
695
Cap 9.65 8.80 11.87 10.55 14.19 12.91 16.45 16.45 18.94 18.94
kW 1.27 1.31 1.35 1.44 1.52
80 (26.7)
470
Cap 8.84 8.06 10.97 9.75 13.24 12.05 15.65 15.65 17.87 17.87
kW 1.34 1.40 1.48 1.55 1.70
560
Cap 9.05 8.25 11.24 9.98 13.55 12.33 15.98 15.98 18.18 18.18
kW 1.33 1.39 1.45 1.51 1.66
695
Cap 9.26 8.44 11.51 10.22 13.85 12.60 16.23 16.23 18.60 18.60
kW 1.32 1.37 1.42 1.48 1.59
Indicates Rating Condition (*Integrated Capacity)
Indicates Integrated Rating
Cap --- Heating Capacity (100 Btuh), Includes indoor fan motor heat
kW --- Total Power Input, includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input
Note: Integrated Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
40KMC, KMQ / 38HDF, QRF