If the outdoor ambient is higher than setting frequency during the oil return, the AC quit oil return.
17.5.9 Low outdoor ambient temperature protection
When compressor is off, T4 is be lower than -35.for 10s, the AC will stop and display LP.
When compressor is on, T4 is be lower than -40.for 10s, the AC will stop and display LP.
When T4 is no lower than -32.for 10s, the unit will exit protection.