Fig. 8 — Base Unit Dimensions — 48AW,AY020-030
NOTES:
1. Weights include economizer (standard).
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
inlet.
Min Clearances to be:
Adjacent Units: 15-0 [4572].
Top of Units: No Overhang.
Condenser Coil: 4-0 [1219].
Economizer Side: 6-0 [1829].
Heat Side: 4-0 [1219].
Filter Access Side: 10-0 [3048]. (For removal of evaporator coil.)
4. For smaller service and operational clearances contact Carrier
Application Engineering Department.
5. Dimensions are in inches [mm].
UNIT SIZE
OPERATING
WEIGHT*
(lbs)
A
(ft-in.)
B
(ft-in.)
CORNER WEIGHT (lbs)
1234
48AW/AY (Low Heat) 020 5182 6- 0
3
/
8
3-6
3
/
16
1090 1183 1514 1395
48AW (High Heat) 020 5262 6- 1
5
/
16
3-6
11
/
16
1134 1203 1505 1419
48AW/AY (Low Heat) 025 5268 5- 9
5
/
8
3-8 1111 1111 1523 1523
48AW (High Heat) 025 5348 5-10
1
/
8
3-8
5
/
16
1144 1128 1527 1548
48AW/AY (Low Heat) 027 5365 5- 9
5
/
8
3-8 1132 1132 1551 1551
48AW (High Heat) 027 5445 5-10
1
/
8
3-8
5
/
16
1165 1149 1555 1577
48AW/AY (Low Heat) 030 5365 5- 9
5
/
8
3-8 1132 1132 1551 1551
48AW (High Heat) 030 5445 5-10
1
/
8
3-8
5
/
16
1165 1149 1555 1577
UNIT SIZE
OPERATING
WEIGHT*
(kg)
A (mm) B (mm)
CORNER WEIGHT (kg)
1234
48AW/AY (Low Heat) 020 2351 1839 1072 495 537 687 633
48AW (High Heat) 020 2387 1862 1085 515 546 683 644
48AW/AY (Low Heat) 025 2390 1768 1118 504 504 691 691
48AW (High Heat) 025 2426 1781 1125 519 512 693 702
48AW/AY (Low Heat) 027 2434 1768 1118 513 513 704 704
48AW (High Heat) 027 2470 1781 1125 528 521 705 715
48AW/AY (Low Heat) 030 2434 1768 1118 513 513 704 704
48AW (High Heat) 030 2470 1781 1125 528 521 705 715