7
Table 1—Physical Data -- Unit 48ES
UNIT SIZE 018040 024040 024060 030040 030060 036060 036090 042060 042090
NOMINAL CAPACITY (ton) 1 --- 1 / 2 2 2 2 --- 1 / 2 2 --- 1 / 2 3 3 3 --- 1 / 2 3 --- 1 / 2
OPERATING WEIGHT lb.
OPERATING WEIGHT (kg)
282
127.9
296
134.2
296
134.2
313
142.0
313
142.0
338
153.3
338
153.3
401
181.9
401
181.9
COMPRESSORS
Quantity
Scroll
1
REFRIGERANT (R---410A)
Quantity (lb.)
Quantity (kg)
5.0
2.3
6.9
3.1
6.9
3.1
8.0
3.6
8.0
3.6
9.2
4.2
9.2
4.2
8.8
4.0
8.8
4.0
REFRIGERANT METERING DEVICE TXV
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
1...21
10.2
2...21
10.2
2...21
10.2
2...21
11.9
2...21
11.9
2...21
13.6
2...21
13.6
2...21
19.4
2...21
19.4
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Diameter (mm)
Motor Hp (Rpm)
2200
22
558.8
1/8 (825)
2200
22
558.8
1/8 (825)
2200
22
558.8
1/8 (825)
2800
22
558.8
1/8 (825)
2800
22
558.8
1/8 (825)
3000
22
558.8
1/8 (825)
3000
22
558.8
1/8 (825)
3500
22
558.8
1/8 (825)
3500
22
558.8
1/8 (825)
EVAPORATOR COIL
Rows...Fins/in.
Face Area (sq ft)
3...17
3.7
3...17
3.7
3...17
3.7
3...17
3.7
3...17
3.7
4...17
3.7
4...17
3.7
3...17
4.7
3...17
4.7
INDOOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Size (mm.)
Motor HP (RPM)
650
10x10
254x254
1/4 (825)
800
10x10
254x254
1/3 (1050)
800
10x10
254x254
1/3 (1050)
1000
10x10
254x254
1/3 (1050)
1000
10x10
254x254
1/3 (1050)
1200
10x10
254x254
1/2 (1000)
1200
10x10
254x254
1/2 (1000)
1400
11x10
279.4x254
1/2 (1075)
1400
11x10
279.4x254
1/2 (1075)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Propane Gas
2...44
2...50
2...44
2...50
2...38
2...46
2...44
2...50
2...38
2...46
2...38
2...46
3...38
3...46
2...38
2...46
2...38
2...46
HIGH--PRESSURE SWITCH
(psig) Cut--out Reset (Auto)
650 +/-- 15
420 +/-- 25
LOSS--OF-- CHARGE / LOW--PRES-
SURE SWITCH (Liquid Line) (psig)
cut--out Reset (auto)
20 +/-- 5
45 +/-- 10
RETURN---AIR FILTERS†}
Throwaway Size (in.)
20x24x1
508x610x25 (mm)
24x30x1
610x762x25 (mm)
24x36x1
610x914x25 (mm)
Table 1—Physical Data Con’t -- Unit 48ES
UNIT SIZE 048090 048115 048130 060090 060115 060130
NOMINAL CAPACITY (ton) 4 4 4 5 5 5
OPERATING WEIGHT lb
OPERATING WEIGHT kg
418
189.6
418
189.6
418
189.6
446
202.3
446
202.3
446
202.3
COMPRESSORS
Quantity
Scroll
1
REFRIGERANT (R--410A)
Quantity (lb.)
Quantity (kg.)
9.0
4.1
9.0
4.1
9.0
4.1
10.5
4.8
10.5
4.8
10.5
4.8
REFRIGERANT METERING DEVICE TXV
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
2...21
19.4
2...21
19.4
2...21
19.4
2...21
19.4
2...21
19.4
2...21
19.4
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Diameter (mm)
Motor Hp (Rpm)
3500
22
558.8
1/4 (1100)
3500
22
558.8
1/4 (1100)
3500
22
558.8
1/4 (1100)
4200
22
558.8
1/4 (1100)
4200
22
558.8
1/4 (1100)
4200
22
558.8
1/4 (1100)
EVAPORATOR COIL
Rows...Fins/in.
Face Area (sq ft)
3...17
5.7
3...17
5.7
3...17
5.7
4...17
5.7
4...17
5.7
4...17
5.7
INDOOR BLOWER
Max 1600 1600 1600 2000 2000 2000
Size (In.)
Size (mm)
11x10
279.4x254
11x10
279.4x254
11x10
279.4x254
11x10
279.4x254
11x10
279.4x254
11x10
279.4x254
Motor HP (RPM) 1/2 (1075) 1/2 (1075) 1/2 (1075) 1.0 (1040) 1.0 (1040) 1.0 (1040)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Propane Gas
3...38
3...46
3...33
3...42
3...31
3...41
3...38
3...46
3...33
3...42
3...31
3...41
HIGH--PRESSURE SWITCH
(psig) Cut--out Reset (Auto)
650 +/-- 15
420 +/-- 25
LOSS--OF--CHARGE / LOW--PRESSURE
SWITCH (Liquid Line) (psig) cut--out Reset
(auto)
20 +/-- 5
45 +/-- 10
RETURN--AIR FILTERS (in.)†}
Throwaway
24x36x1
610x914x25 (mm)
*Based on altitude of 0 to 2000 ft.
{ Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/
minute for throwaway type or 450 ft/minute for high--capacity type. Air filter pre ssure drop for non--standard filters m ust not exceed 0.08 in. wc.
} If usin g accessory filter rack re fer to the filter rack installation instructions for correct filter sizes and quantity.
48ES