52
STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET
LEGEND
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker per NEC.
**Units have 2 condenser-fan motors.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. The UL, Canada units may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature
± 10% voltage.
UNIT
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR OFM IFM
COMBUSTION
FAN MOTOR
POWER
SUPPLY
WITH OUTLET
MINIMUM UNIT
DISCONNECT
SIZE*
Min Max RLA LRA FLA FLA FLA MCA MOCP FLA LRA
48HJE/HJF004
(3 Tons)
208/230-1-60 187 254 16.0 88.0 0.7 4.9 .57 31.6/31.6 40/40† 30/30 106/106
208/230-3-60 187 254 10.3 77.0 0.7 4.9 .57 24.5/24.5 30/30† 24/24 95/95
460-3-60 414 508 5.1 39.0 0.4 2.2 .30 11.7 15† 11 48
575-3-60 518 632 4.2 31.0 0.4 2.2 .30 9.5 15† 938
48HJD/HJE/HJF005
(4 Tons)
208/230-1-60 187 254 23.7 129.0 0.7 4.9 .57 41.2/41.2 50/50† 39/39 147/147
208/230-3-60 187 254 13.5 99.0 0.7 4.9 .57 28.5/28.5 35/35† 27/27 117/117
460-3-60 414 508 7.4 49.5 0.4 2.2 .30 14.6 20† 14 58
575-3-60 518 632 5.8 40.0 0.4 2.2 .30 11.5 15† 11 47
48HJD/HJE/HJF006
(5 Tons)
208/230-1-60 187 254 28.8 169.0 1.5 8.8 .57 52.3/52.3 60/60† 50/50 221/221
208/230-3-60 187 254 17.3 123.0 1.5 5.8 .57 34.9/34.9 40/40† 34/34 173/173
460-3-60 414 508 9.0 62.0 0.8 2.6 .30 17.4 20† 17 86
575-3-60 518 632 7.1 50.0 0.8 2.6 .30 13.8 20† 13 69
48HJD/HJE/HJF007
(6 Tons)
208/230-3-60 187 254 20.5 156.0 1.4 5.8 .57 38.8/38.8 45/45† 35/35 205/205
460-3-60 414 508 9.6 70.0 0.6 2.6 .30 17.9 20† 17 94
575-3-60 518 632 7.7 56.0 0.6 2.6 .30 14.3 20† 15 79
48HJD/HJE/HJF008
(7
1
/
2
Tons)**
208/230-3-60 187 254 12.4 88.0 1.4 7.5 .57 44.2/44.2 50/50† 46/46 247/247
460-3-60 414 508 6.4 44.0 0.7 3.4 .30 21.9 25† 23 124
575-3-60 518 632 4.8 34.0 0.7 3.4 .30 16.8 20† 17.5 97
48HJD/HJE/HJF009
(8
1
/
2
Tons)**
208/230-3-60 187 254 15.0 99.0 1.4 7.5 .57 50.1/50.1 60/60† 52/52 269/269
460-3-60 414 508 8.2 49.5 0.7 3.4 .30 26.0 30† 27 135
575-3-60 518 632 5.8 40.0 0.7 3.4 .30 19.1 25† 20 109
48HJD/HJE/HJF012
(10 Tons)**
208/230-3-60 187 254 17.3 123.0 1.4 10.6 .57 58.3/58.3 70/70 61/61 341/341
460-3-60 414 508 9.0 62.0 0.7 4.8 .30 29.2 35† 30 172
575-3-60 518 632 7.1 50.0 0.7 4.8 .30 23.1 25† 24 139
48HJD/HJE014
(12
1
/
2
Tons)**
208/230-3-60 187 254 19.0 156.0 1.4 15.0 .57 66.6/66.6 70/70 70/70 430/430
460-3-60 414 508 9.0 70.0 0.7 7.4 .30 31.8 35† 33 199
575-3-60 518 632 7.4 54.0 0.7 7.4 .30 25.9 30† 27 156
FLA —
Full Load Amps
HACR —
Heating, Air Conditioning and Refrigeration
IFM —
Indoor (Evaporator) Fan Motor
LRA —
Locked Rotor Amps
MCA —
Minimum Circuit Amps
MOCP —
Maximum Overcurrent Protection
NEC —
National Electrical Code
OFM —
Outdoor (Condenser) Fan Motor
RLA —
Rated Load Amps
UL —
Underwriters’ Laboratories
Electrical data (cont)