STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET
LEGEND
*Used to determine minimum disconnect per NEC.
Fuse or HACR circuit breaker per NEC.
**Units have 2 condenser-fan motors.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. The UL, Canada units may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature
± 10% voltage.
UNIT
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR OFM IFM
COMBUSTION
FAN MOTOR
POWER
SUPPLY
WITH OUTLET
MINIMUM UNIT
DISCONNECT
SIZE*
Min Max RLA LRA FLA FLA FLA MCA MOCP FLA LRA
48HJE/HJF004
(3 Tons)
208/230-1-60 187 254 16.0 88.0 0.7 4.9 .57 31.6/31.6 40/40 30/30 106/106
208/230-3-60 187 254 10.3 77.0 0.7 4.9 .57 24.5/24.5 30/30 24/24 95/95
460-3-60 414 508 5.1 39.0 0.4 2.2 .30 11.7 15 11 48
575-3-60 518 632 4.2 31.0 0.4 2.2 .30 9.5 15 938
48HJD/HJE/HJF005
(4 Tons)
208/230-1-60 187 254 23.7 129.0 0.7 4.9 .57 41.2/41.2 50/50 39/39 147/147
208/230-3-60 187 254 13.5 99.0 0.7 4.9 .57 28.5/28.5 35/35 27/27 117/117
460-3-60 414 508 7.4 49.5 0.4 2.2 .30 14.6 20 14 58
575-3-60 518 632 5.8 40.0 0.4 2.2 .30 11.5 15 11 47
48HJD/HJE/HJF006
(5 Tons)
208/230-1-60 187 254 28.8 169.0 1.5 8.8 .57 52.3/52.3 60/60 50/50 221/221
208/230-3-60 187 254 17.3 123.0 1.5 5.8 .57 34.9/34.9 40/40 34/34 173/173
460-3-60 414 508 9.0 62.0 0.8 2.6 .30 17.4 20 17 86
575-3-60 518 632 7.1 50.0 0.8 2.6 .30 13.8 20 13 69
48HJD/HJE/HJF007
(6 Tons)
208/230-3-60 187 254 20.5 156.0 1.4 5.8 .57 38.8/38.8 45/45 35/35 205/205
460-3-60 414 508 9.6 70.0 0.6 2.6 .30 17.9 20 17 94
575-3-60 518 632 7.7 56.0 0.6 2.6 .30 14.3 20 15 79
48HJD/HJE/HJF008
(7
1
/
2
Tons)**
208/230-3-60 187 254 12.4 88.0 1.4 7.5 .57 44.2/44.2 50/50 46/46 247/247
460-3-60 414 508 6.4 44.0 0.7 3.4 .30 21.9 25 23 124
575-3-60 518 632 4.8 34.0 0.7 3.4 .30 16.8 20 17.5 97
48HJD/HJE/HJF009
(8
1
/
2
Tons)**
208/230-3-60 187 254 15.0 99.0 1.4 7.5 .57 50.1/50.1 60/60 52/52 269/269
460-3-60 414 508 8.2 49.5 0.7 3.4 .30 26.0 30 27 135
575-3-60 518 632 5.8 40.0 0.7 3.4 .30 19.1 25 20 109
48HJD/HJE/HJF012
(10 Tons)**
208/230-3-60 187 254 17.3 123.0 1.4 10.6 .57 58.3/58.3 70/70 61/61 341/341
460-3-60 414 508 9.0 62.0 0.7 4.8 .30 29.2 35 30 172
575-3-60 518 632 7.1 50.0 0.7 4.8 .30 23.1 25 24 139
48HJD/HJE014
(12
1
/
2
Tons)**
208/230-3-60 187 254 19.0 156.0 1.4 15.0 .57 66.6/66.6 70/70 70/70 430/430
460-3-60 414 508 9.0 70.0 0.7 7.4 .30 31.8 35 33 199
575-3-60 518 632 7.4 54.0 0.7 7.4 .30 25.9 30 27 156
FLA
Full Load Amps
HACR
Heating, Air Conditioning and Refrigeration
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
NEC
National Electrical Code
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
UL
Underwriters Laboratories
Electrical data (cont)