Table
2
Electrical
Data
UNIT
NOMINAL
V-PH-HZ
IFM
TYPE
VOLTAGE
RANGE
COMPR
(each)
OFM
IFM
COMBUSTION
FAN
MOTOR
POWER
SUPPLY
DISCONNECT
SIZE
Ml
msnm
IH23
W3WM
FLA
MCA
MOCP*
FLA
LRA
48LJE/LJF004
(3
Tons)
208/230-1
-60
Std
187
254
179
93
1
9
mm
57
27
1/27
1
35/35
26/26
105/105
Alt
28.1/28
1
35/35
27/27
107/107
208/230-3-60
Std
187
254
11
2
80
1
9
28
.57
18
7/18.7
25/25
18/18
92/92
Alt
38
19
7/19.7
25/25
19/19
94/94
460-3-60
Std
414
508
6
1
40
1
0
1
5
30
101
15
10
46
Alt
1.9
105
15
10
46
575-3-60
Std
518
632
45
29
1
9
2.8
57
7.5
15
7
34
Alt
38
7.9
15
8
34
48LJD/LJE/LJF
005
(4
Tons)
208/230-1-60
Std
187
254
24
8
127
1
9
38
57
36
7/36.7
45/45
35/35
141/141
Alt
57
38.6/38
6
45/45
37/37
144/144
208/230-3-60
Std
187
254
157
99
1.9
3.8
57
25
3/25.3
30/30
25/25
113/113
Alt
5.7
27
2/27.2
35/35
27/27
116/116
460-3-60
Std
414
508
78
50
1
0
1
9
.30
126
15
12
56
Alt
2.8
13.5
20
13
58
575-3-60
Std
518
632
55
40
1.9
38
57
9.2
15
9
45
Alt
5.7
9.9
15
10
47
48LJD/LJE/LJF
006
(5
Tons)
230-1
-60
Std
187
254
27.8
135
1
9
85
.57
45
2
60
44
164
208/230-3-60
187
254
19.2
105
1
9
8.5
.57
34.4/34.4
40/40
34/34
134/134
460-3-60
414
508
96
55
1
0
4.5
30
17.5
20
17
81
575-3-60
518
632
83
45
1
9
85
.57
14.5
20
14
57
48LJD/LJE/LJF
007
(6
Tons)
208/230-3-60
Std
187
254
21
9
142
1
9
5.8
57
35.1/35.1
40/40
34/34
188/188
460-3-60
414
508
104
72
1
0
2.6
30
16.6
20
16
95
575-3-60
518
632
96
58
5
1
9
11
0
57
172
20
17
81
IMPORTANT:
Optional,
alternate
evaporator-fan
motor
and
drive
are
not
available
for
48LJ006,007
units.
Contact
your
local
Carrier
representative
for
more
information
about
field-installed
motors
LEGEND
COMPR
FLA
HACR
IFM
LRA
MCA
MOCP
OFM
RLA
Compressor
Full
Load
Amps
Heating,
Air
Conditioning
and
Refrigeration
Indoor
(Evaporator)
Fan
Motor
Locked
Rotor
Amps
Minimum
Circuit
Amps
Maximum
Overcurrent
Protection
Outdoor
(Condenser)
Fan
Motor
Rated
Load
Amps
‘Fuse
or
HACR
circuit
breaker
NOTES:
1.
In
compliance
with
NEC
(National
Electrical
Code)
requirements
for
multi¬
motor
and
combination
load
equipment
(refer
to
NEC
Articles
430
and
440),
the
overcurrent
protective
device
for
the
unit
shall
be
fuse
or
HACR
breaker
Canadian
Standards
Association
(CSA)
units
may
be
fuse
or
circuit
breaker
2
Unbalanced
3-Phase
Supply
Voltage
Never
operate
a
motor
where
a
phase
imbalance
in
supply
voltage
is
greater
than
2%
Use
the
following
formula
to
determine
the
percent
voltage
im¬
balance.
%
Voltage
Imbalance
=
100
x
max
voltage
deviation
from
average
voltage
average
voltage
Example:
Supply
voltage
is
460-3-60.
AB
=
452
v
BC
=
464v
AC
=
455
v
452
+
464
+
455
Average
Voltage
--
_
1371
3
=
457
NOTE:
The
575-v
units
are
CSA
only
Determine
maximum
deviation
from
average
voltage
(AB)
457
-
452
=
5
v
(BC)
464
-
457
=
7
V
(AC)
457
-
455
=
2
V
Maximum
deviation
is
7
v.
Determine
%
voltage
imbalance
7
%
Voltage
Imbalance
=
100
x
457
=
1
53%
This
amount
of
phase
imbalance
is
satisfactory
as
it
is
below
the
maximum
allowable
2%
IMPORTANT:
If
the
supply
voltage
phase
imbalance
is
more
than
2%,
contact
your
local
electric
utility
company
immediately
8