12—Model
48N
Air
Delivery
(Cfm)
at
Indicated
External
Static
Pressure
&
Voltage
(Sizes
48NLT018
thru
48NHT048)
End
Discharge
External
Static
Pressure—Inches
Water
48N
Motor
I
208V
H
230V
or
460V
Volt/Ph/Hz
Speed
0.0
0.1
0.2
0.3
0.4
0.5
0.0
0.1
0.2
0.3
0.4
0.5
48NLT018,
48NLT024,
48NHT024
A*
Low
712
700
689
680
663
651
750
737
726
716
700
686
208/230-1-60
•t
Med
1185
1129
1088
1026
979
922
1256
1195
1148
1081
1031
971
Hi
1370
1291
1221
1142
1063
1003
1442
1359
1285
1202
1119
1056
48NLT030,
48NMT030
At
Low
735
726
689
675
775
763
751
740
726
711
208/230-1-60
•t
Med
1184
1163
1150
1226
1211
1194
1164
1120
Hi
1443
1279
1197
1519
1489
1449
1399
1347
1261
48NHT030,
LT036
48NMT036,
LT042
At
Low
1002
854
796
1056
1022
986
946
900
839
48NMT042
208/230-1-60
•t
Med
1515
1452
1389
1308
BBS
1464
1378
1293
1164
208/230-3-60,
460-3-60
Hi
1764
S3
1857
1795
1708
1603
1457
1321
48NHT036,
NVT036
48NHT042
A
Low
1610
1570
1504
1435
1358
1260
1787
1733
1641
1559
1458
1345
208/230-1-60
208/230-3-60
Med
1913
1820
1736
1645
1544
1428
1909
1806
1714
1603
1495
460-3-60f
Hi
2032
1942
1844
1759
1636
1514
1983
1883
1782
1665
1545
48NLT048,
NMT048
48NHT048
A
Low
1627
1589
1527
1449
1364
1282
1807
1758
1704
1607
1518
1404
208/230-3-60
Med
1945
1880
1796
1708
1611
1508
2061
1970
1892
1813
1704
1580
460-3-60t
Hi
2138
2045
1943
1846
1738
1624
2178
2081
1941
1869
1769
1650
(Applicable
notes
are
listed
below
Table
13.)
Table
13—Down
Discharge
External
Static
Pressure—Inches
Water
48N
Motor
i
208V
230V
or
460V
Volt/Ph/Hz
Speed
0.0
0.1
0.2
0.3
0.4
0.5
0.0
0.1
0.2
0.3
0.4
0.5
48NLT018
48NLT024,
48NHT024
At
Low
705
692
684
671
657
639
743
730
721
707
693
674
208/230-1-60
•t
Med
1138
1102
1045
996
942
889
1196
1161
1101
1050
993
932
Hi
1308
1234
1162
1084
1020
951
1379
1301
1225
1143
1075
1002
48NLT030,
48NMT030
At
Low
724
715
706
695
682
665
763
754
744
733
719
701
208/230-1-60
•t
Med
1155
1138
1120
1104
1073
1031
1218
1200
1182
1165
1132
1088
Hi
1411
1362
1326
1249
1195
1133
1493
1457
1412
1358
1274
1218
48NHT030,
LT036
48NMT036,
LT042,
At
Low
969
947
911
863
816
760
1022
998
960
910
860
801
48NMT042
208/230-1-60
•t
Med
1494
1430
1358
1273
1174
1058
1574
1507
1431
1341
1237
1115
208/230-3-60,
460-3-60t
Hi
1683
1615
1536
1440
1274
1153
1763
1700
1619
1492
1343
1215
48NHT036,
NVT036
48NHT042,
NVT048
A
Low
1534
1493
1430
1359
1280
1200
1704
1638
1553
1468
1390
1304
208/230-1-60
208/230-3-60
Med
1797
1709
1620
1547
1448
1315
1855
1707
1684
1574
1498
1361
460-3-60f
Hi
1885
1779
1704
1608
1507
1404
1906
1821
1722
1623
1533
1410
48NLT048,
48NMT048
48NHT048
208/230-1-60
A
Low
1539
1515
1466
1410
1325
1229
1735
1688
1613
1539
1440
1334
208/230-3-60
208/230-3-60
Med
1833
1768
1700
1599
1505
1390
1918
1849
1752
1670
1561
1442
460-3-60t
Hi
1957
1873
1786
1907
1817
1713
1618
1506
Factory
blower
motor
speed
setting
for
cooling
operation.
A
Factory
blower
motor
speed
setting
for
heating
operation.
*Air
delivery
values
are
without
air
filter
and
are
for
dry
coil.
See
Table
16
for
wet
coil
pressure
drop.
Deduct
field-supplied
air
filter
pressure
drop
and
wet
coil
pressure
drop
to
obtain
external
static
pressure
available
for
ducting.
|460
volt
units
high
speed
only.
Do
not
change
blower
speed
settings.
tFor
208V
operation,
change
the
blower
motor
speed
setting
to
the
next
higher
speed.
See
steps
6
and
9.
NOTE:
Do
not
operate
the
unit
at
a
cooling
airflow
that
is
less
than
350
cfm
per
each
12,000
Btuh
of
rated
cooling
capacity.
Indoor
coil
icing
may
occur
at
airflows
below
this
point.