FLARE
NUT
STRAINER
RETAINER
COOLING
FLARE
NUT
A87277
Fig.
15—Metering
Device
Components
Table
19—Cooling
Service
Analysis
Chart
SYMPTOM
CAUSE
REMEDY
Compressor
and
condenser
fan
will
not
start.
Power
failure
Call
power
company.
Fuse
blown
or
circuit
breaker
tripped
Replace
fuse
or
reset
circuit
breaker.
Defective
thermostat,
contactor,
transformer,
or
control
relay
Replace
component.
Insufficient
line
voltage
Determine
cause
and
correct.
Incorrect
or
faulty
wiring
Check
wiring
diagram
and
rewire
correctly.
Thermostat
setting
too
high
Lower
thermostat
setting
below
room
temperature.
Compressor
will
not
start
but
condenser
fan
runs.
Faulty
wirjng
or
loose
connections
in
compressor
circuit
Check
wiring
and
repair
or
replace.
Compressor
motor
burned
out,
seized,
or
internal
overload
open
Determine
cause.
Replace
compressor.
Defective
run/start
capacitor,
overload,
start
relay
Determine
cause
and
replace.
One
leg
of
three-phase
power
dead
Replace
fuse
or
reset
circuit
breaker.
Determine
cause.
Compressor
cycles.
(other
than
normally
satisfying
thermostat)
Refrigerant
overcharge
or
undercharge
Blow
refrigerant,
evacuate
system,
and
recharge
to
nameplate.
Defective
compressor
Replace
and
determine
cause.
Insufficient
line
voltage
Determine
cause
and
correct.
Blocked
condenser
Determine
cause
and
correct.
Defective
run/start
capacitor,
overload,
or
start
relay
Determine
cause
and
replace.
Defective
thermostat
Replace
thermostat.
Faulty
condenser
fan
motor
or
capacitor
Replace.
Restriction
in
refrigerant
system
Locate
restriction
and
remove.
Compressor
operates
continuously.
Dirty
air
filter
Replace
filter.
Unit
undersized
for
load
Decrease
load
or
increase
unit
size.
Thermostat
set
too
low
Reset
thermostat.
Low
refrigerant
charge
Locate
leak,
repair,
and
recharge.
Leaking
valves
in
compressor
Replace
compressor.
Air
in
system
Blow
refrigerant,
evacuate
system,
and
recharge.
Condenser
coil
dirty
or
restricted
Clean
coil
or
remove
restriction.
Excessive
head
pressure
Dirty
air
filter
Replace
filter.
Dirty
condenser
coil
Clean
coil.
Refrigerant
overcharged
Purge
excess
refrigerant.
Air
in
system
Blow
refrigerant,
evacuate
system,
and
recharge.
Condenser
air
restricted
or
air
short-cycling
Determine
cause
and
correct.
Head
pressure
too
low
Low
refrigerant
charge
Check
for
leaks,
repair,
and
recharge.
Compressor
valves
leaking
Replace
compressor.
Restriction
in
liquid
tube
Remove
restriction.
Excessive
suction
pressure
High
heat
load
Check
for
source
and
eliminate..
Compressor
valves
leaking
Replace
compressor.
Refrigerant
overcharged
Purge
excess
refrigerant.
Dirty
air
filter
Replace
filter.
Low
refrigerant
charge
Check
for
leaks,
repair,
and
recharge.
Metering
device
or
low
side
restricted
Remove
source
of
restriction.
Suction
pressure
too
low
Insufficient
evaporator
airflow
Increase
air
quantity.
Check
filter—replace
if
necessary.
Temperature
too
low
in
conditioned
area
Reset
thermostat.
Outdoor
ambient
below
55
F
Install
low-ambient
kit.
Field-installed
filter-drier
restricted
Replace.
Manufacturer
reserves
the
right
to
discontinue,
or
change
at
any
time,
specifications
or
designs
without
notice
and
without
incurring
obligations.