EasyManua.ls Logo

Carrier 48NHT024 - Preparing Unit for Startup

Carrier 48NHT024
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.
Insulate
low-voltage
wires
for
highest
voltage
con¬
tained
within
conduit
when
low-voltage
control
wires
are
run
in
same
conduit
as
high-voltage
wires.
5.
Do
not
damage
internal
components
when
drilling
thru
any
panel
to
mount
electrical
hardware,
conduit,
etc.
A.
High-Voltage
Connections
The
unit
must
have
a
separate
electrical
service
with
a
field-
supplied,
waterproof,
fused
disconnect
switch
mounted
at,
or
within
sight
from
the
unit.
Refer
to
the
unit
rating
plate
for
maximum
fuse
size
and
minimum
circuit
amps
(ampac¬
ity)
for
wire
sizing.
Tables
2
thru
7
show
recommended
wire
sizes
based
on
rating
plate
data.
The
field-supplied
disconnect
switch
box
may
be
mounted
on
the
unit
over
the
high-voltage
inlet
hole
in
the
control
corner
panel.
See
Figs.
2
and
3.
Proceed
as
follows
to
complete
the
high-voltage
connections
to
the
unit:
1.
Connect
ground
lead
to
chassis
ground
connection
when
using
separate
ground
wire.
2.
Run
high-voltage
leads
into
unit
control
box
and
con¬
nect
to
contactor.
See
unit
wiring
label,
and
Fig.
8.
B.
Special
Procedures
for
208-V
Operation
A
WARNING
Make
sure
that
the
power
supply
to
the
unit
is
switched
OFF
before
making
any
wiring
changes.
Electrical
shock
can
cause
personal
injury
or
death.
For
operation
on
208
volts,
disconnect
the
orange
transformer-primary
lead
from
the
contactor.
See
the
unit
wiring
label.
Remove
the
tape
and
cover
from
the
terminal
on
the
end
of
the
red
transformer-primary
lead.
Save
the
cover.
Connect
the
red
lead
to
the
contactor
terminal
from
which
the
orange
lead
was
disconnected.
Using
the
cover
removed
from
the
red
lead,
insulate
the
loose
terminal
on
the
orange
lead.
Wrap
the
cover
with
elec¬
trical
tape
so
that
the
metal
terminal
can
not
be
seen.
Indoor
blower
motor
speed
taps
should
be
changed
for
208V
operation
on
208/230v
rated
units.
Interchange
motor
leads
at
printed
circuit
board
(PCI)
in
unit
control
box.
High
speed
for
cooling
and
medium
speed
for
heating
operation.
See
Step
9-C
and
unit
wiring
label.
Do
not
change
blower
speed
setting
for
460V
rated
units.
C.
Control
Voltage
Connections
Locate
the
room
thermostat
on
an
inside
wall
in
the
space
to
be
conditioned
where
it
will
not
be
subjected
to
either
a
cooling
or
heating
source
or
direct
exposure
to
sunlight.
Mount
the
thermostat
4
to
5-ft
above
the
floor.
Use
No.
18
AWG
color-coded,
insulated
(35
C
minimum)
wires
to
make
the
control
voltage
connections
between
the
thermostat
and
the
unit.
If
the
thermostat
is
located
more
than
100-ft
from
the
unit
(as
measured
along
the
control
voltage
wires),
use
No.
16
AWG
color-coded,
insulated
(35
C
minimum)
wires.
A
grommeted,
control
voltage
inlet
hole
is
located
in
the
panel
adjacent
to
the
control
access
panel.
See
Figs.
2
and
3.
Run
the
low-voltage
leads
from
the
thermostat,
thru
the
inlet
hole,
and
to
the
control
voltage
terminals
through
a
hole
in
the
bottom
of
the
unit
control
box.
Pass
control
volt¬
age
leads
through
wire
ties
located
under
unit
control
box.
Connect
the
thermostat
leads
to
the
terminals
as
shown
in
Fig.
8.
D.
Heat
Anticipator
Setting
The
room
thermostat
heat
anticipator
must
be
properly
adjusted
to
ensure
proper
heating
performance.
Set
the
heat
anticipator,
using
an
ammeter
to
determine
the
exact
required
setting.
NOTE:
For
thermostat
selection
purposes,
use
1.0
amp
for
the
approximate
required
setting.
THERMOSTAT
(TYPICAL)
(w)(y)(g)(r)@
!
I
I
I
I
!
I
I
—TERMINAL
BOARD
<2^
r
CONTROL
BOX
Jr
GND
r
CONTACTOR
TERMINALS
1
(SEE
UNIT
WIRING
LABEL)
FIELD
SUPPLIED
FUSED
DISCONNECT
-
3-PHASE
UNITS
ONLY
FIELD
CONTROL-VOLTAGE
WIRING
'
FIELD
HIGH-VOLTAGE
WIRING
A87380
Fig.
8—High
and
Control
Voltage
Connections
Failure
to
make
a
proper
heat
anticipator
adjustment
will
result
in
improper
operation,
discomfort
to
the
occupants
of
the
conditioned
space,
and
inefficient
energy
utilization;
however,
the
required
setting
may
be
changed
slightly
to
provide
a
greater
degree
of
comfort
for
a
particular
installation.
E.
C
i
r
cuit
Breaker
Unit
has
manual
reset
circuit
breaker
which
is
located
in
the
low
voltage
wiring
box
adjacent
to
low
voltage
terminal
board.
If
unit
fails
to
operate,
first
check
breaker
for
tripped
position.
If
breaker
is
tripped,
re-set
and
try
to
start
unit.
If
breaker
continues
to
trip
there
is
a
problem
in
the
low
volt¬
age
electrical
circuit.
(Electrical
short,
ground,
or
trans¬
former
overload)
Correct
the
condition
and
check
for
normal
unit
operation.
Step
7—Preparing
Unit
for
Startup
A
WARNING
DANGER:
Failure
to
observe
the
following
warnings
could
result
in
serious
personal
injury:
1.
Follow
recognized
safety
practices
and
wear
protec¬
tive
goggles
when
checking
or
servicing
refrigerant
system.
2.
Do
not
operate
compressor
or
provide
any
electric
power
to
unit
unless
compressor
terminal
cover
is
in
place
and
secured.
3.
Do
not
remove
compressor
terminal
cover
until
all
electrical
sources
have
been
disconnected.
4.
Relieve
all
pressure
from
system
before
touching
or
disturbing
anything
inside
terminal
box
if
refriger¬
ant
leak
is
suspected
around
compressor
terminals.
5.
Never
attempt
to
repair
soldered
connection
while
refrigerant
system
is
under
pressure.
6.
Do
not
use
torch
to
remove
any
component.
System
contains
oil
and
refrigerant
under
pressure.
To
remove
a
component,
wear
protective
goggles
and
proceed
as
follows:
a.
Shut
off
gas
supply
and
then
electrical
power
to
unit.
b.
Relieve
all
pressure
from
system.
c.
Cut
component
connecting
tubing
with
tubing
cutter
and
remove
component
from
unit.
d.
Carefully
unsweat
remaining
tubing
stubs
when
necessary.
Oil
can
ignite
when
exposed
to
torch
flame.
9

Related product manuals