103
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — OPERATING MODES (cont)
MODE — ALARMS
ITEM EXPANSION RANGE UNITS
CCN TABLE/
SUB-TABLE
CCN
POINT
WRITE
STATUS
OPERATING MODES (cont) MAINTENANCE DISPLAY
ECON Economizer Diagnostic ECONDIAG
EC.EN Economizer Installed Yes/No ECONO
OCC Currently Occupied Yes/No OCCUPIED Forcible
IDF Indoor Fan Relay On/Off IDF
COOL In Cooling Mode? Yes/No IN_COOL
E.LOC Econo Cool OAT Lockout Yes/No ECONLOCK
EH.LO Econo Cool Hi Temp Limit 40 to 100 F dF OATLECLH
EL.LO Econo Cool Lo Temp Limit 0 to 50 F dF OATLECLL
FC.LO Free Cool Low Temp Limit 0 to 70 F dF OATLUEFC
EN.LO Econo Cool Enth Lockout Yes/No ENTHLOCK
EC.MX Econo Cool Max Position 0 to 100 % ECONOMAX
EC.MN Econo Minimum Position 0 to 100 % ECONOMIN
AQ.DV IAQ DCV Mode Yes/No IN_IAQDV
AQ.MN Econo Min IAQ Position 0 to 100 % IAQMINP
AQ.OV IAQ Override Mode Yes/No IN_IAQOV
OVR.P IAQ Overide Position 0 to 100 % IAQOVPOS
AQ.LO OAQ Lockout Mode Yes/No IN_OAQLO
OAQ.L OAQ Lockout Limit 0 to 5000 OAQLOCK
LP.OV Lo Refrig Press Override Yes/No IN_LPOV
EC.CP Econo Commanded Position xxx % ECONOCMD Forcible
EC.AP Econo Actual Position xxx % ECONOPOS
EC.MP Min Position in Effect xxx % MIN_POS
E.CAL Economizer Calibrating Yes/No ECOINCAL
(Display TRIM — see Sensor Calibration TRIM
Calibration)
(TRIM=CCN Only) Space Temp Calibration –30 to 130 dF SPT_CAL Forcible
Space Temp Trim –30 to 30 ^F SPT_OFF Forcible
Supply Air Temp Calib. –30 to 130 dF SAT_CAL Forcible
Supply Air Temp Trim –30 to 30 ^F SAT_OFF Forcible
Return Air Temp Calib. –30 to 130 dF RAT_CAL Forcible
Return Air Temp Trim –30 to 30 ^F RAT_OFF Forcible
(OCCDEFM = CCN only) Occupancy Supervisory OCCDEFM
Current Mode (1=Occup) 0,1 MODE
Current Occup Period # 0 to 8 PER_NO
Time-Override in Effect Yes/No OVERLAST
Time-Override Duration 0 to 4 hours OVR_HRS
Current Occupied Tiime xx.xx hh.mm STRTTIME
Current Unoccupied Time xx.xx hh.mm ENDTIME
Next Occupied Day NXTOCDAY
Next Occupied Time xx.xx hh.mm NXTOCTIM
Next Unoccupied Day NXTUNDAY
Next Unoccupied Time xx.xx hh.mm NXTUNTIM
Previous Unoccupied Day PRVUNDAY
Previous Unoccupied Time xx.xx hh.mm PRVUNTIM
OPERATING MODES MAINTENANCE DISPLAY
(LINKDATA = CCN only) CCN — Linkage LINKDATA
Supervisory Element # xxx SUPE-ADR
Supervisory Bus xxx SUPE-BUS
Supervisory Block Number xxx BLOCKNUM
Average Occup. Heat Stp. xxx.x dF AOHS
Average Occup. Cool Stp. xxx.x dF AOCS
Average Unocc. Heat Stp. xxx.x dF AUHS
Average Unocc. Cool Stp. xxx.x dF AUCS
Average Zone Temperature xxx.x dF AZT
Average Occup. Zone Temp xxx.x dF AOZT
Linkage System Occupied? Yes/No LOCC
Next Occupied Day Mon-Sun LNEXTOCD
Next Occupied Time xx:xx hh.mm LNEXTOCC Forcible
Next Unoccupied Day Mon-Sun LNEXTUOD
Next Unoccupied Time xx.xx hh.mm LNEXTUNC Forcible
Last Unoccupied Day Mon-Sun LLASTUOD
Last Unoccupied Time xx.xx hh.mm LLASTUNC Forcible
ITEM EXPANSION RANGE DEFAULT
CCN TABLE/
SUB-TABLE
CCN
POINT
WRITE
STATUS
ALARMS ALARMS
R.CURR Reset All Current Alarms Yes/No No ALRESET Forcible
R.HIST Reset Alarm History Yes/No No ALHISCLR Forcible
CURR Currently Active Alarms
alarm# text string
(repeat up to 25 alarms)
HIST Alarm History ALARM HISTORY
alarm# alarm#-mm/dd/yy-hh.mm-text string
(repeat up to 20 Alarms)