CL-5
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE DEFAULT ENTRY
CONFIGURATION (cont)
TRIM Sensor Calibration
SPT.C Space Temp Calibration –30 to 120 dF
SPT.T Space Temp Trim –30 to 30 ^F 0
SAT.C Supply Air Temp Calib. –30 to 130 dF
SAT.T Supply Air Temp Trim –30 to 30 ^F 0
RAT.C Return Air Temp Calib. –30 to 130 dF
RAT.T Return Air Temp Trim –30 to 30 ^F 0
CCN CCN Configuration
CCN.A CCN Element Number 1 to 239 1
CCN.B CCN Bus Number 0 to 239 0
BAUD CCN Baud Rate 1=2400
2=4800
3=9600
4=19200
5=38400
3
BROD CCN Broadcast
Configuration
B.TIM CCN Time/Date
Broadcast
Yes/No No
B.OAT CCN OAT Broadcast Yes/No No
B.GS Global Schedule
Broadcast
Yes/No No
B.ACK CCN Broadcast Ack'er Yes/No No
SCH.O CCN Schedule Overrides
SCH.N Schedule Number 0=Always Occupied
1 to 64=Local Schedule
65 to 99=Global Schedule
0
HOL.G Accept Global Holidays Yes/No No
OV.TL Override Time Limit 0 to 4 hours 1
OV.EX Timed Override Hours 0 to 4 hours 0
OV.SP SPT Override Enabled Yes/No Yes

Table of Contents