94
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — RUN STATUS (cont)
ITEM EXPANSION RANGE UNITS
CCN TABLE/
SUB-TABLE
CCN
POINT
WRITE
STATUS
RUN STATUS (cont)
COOL (cont)
CIR.B Refrigerant Circuit B
CMP.B Compressors B On/Off COMP_B
TG.B Timeguard B xxx sec TIMGD_B
CS.B1 Compressor B1 Feedback On/Off CS_B1
RH2.B Reheat2 Valve B,C On/Off RH2_B
SST.B Sat. Suction Temp B xxx.x dF SST_B
SSP.B Suction Pressure B xxx.x psig SSP_B
SCT.B Sat. Condenser Temp B xxx.x dF SCT_B
SCP.B Condenser Pressure B xxx.x psig SCP_B
CIR.C Refrigerant Circuit C
CMP.C Compressors C On/Off COMP_C
TG.C1 Timeguard C xxx sec TIMGD_C
CS.C1 Compressor C1 Feedback On/Off CS_C1
RH2.C Reheat2 Valve B,C On/Off RH2_C
SST.C Sat. Suction Temp C xxx.x dF SST_C
SSP.C Suction Pressure C xxx.x psig SSP_C
SCT.C Sat. Condenser Temp C xxx.x dF SCT_C
SCP.C Condenser Pressure C xxx.x psig SCP_C
HEAT Heating Status HEATDISP
DMD.H Heating Demand xxx.x ^F HEAT_DMD
AVL.H Available Heating Stages x AVLHSTGS
REQ.H Requested Heating Stages x REQHSTGS
IDF Indoor Fan Relay On/Off IDF
HT.1 Heat Stage 1 Relay On/Off HEAT_1
TG.H1 Heat Stage 1 Timeguard xxx sec TIMGD_H1
HT.2 Heat Stage 2 Relay On/Off HEAT_2
TG.H2 Heat Stage 2 Timeguard xxx sec TIMGD_H2
ECON Economizer Status ECONDISP
EC.CP Econo Commanded Position xxx % ECONOCMD
EC.AP Econo Actual Position xxx % ECONOPOS
EC.MP Minimum Position in Effect xxx % MIN_POS
IAQ.S IAQ Level (Switch) High/Low IAQIN
IAQ IAQ Level (Sensor) xxxx ppm IAQ
OAT Outdoor Air Temperature xxx.x dF OA_TEMP
ENTH Outdoor Enthalpy Switch High/Low ENTHALPY
OAQ OAQ Level (Sensor) xxxx ppm OAQ
PE.1 Power Exhaust 1 Relay On/Off PE_1
PE.2 Power Exhaust 2 Relay On/Off PE_2
(LON_DATA = CCN only) LON Communication Status LON_DATA
nviSpaceTemp xxx.x dF NVI_SPT Forcible
nviSetPoint xxx.x dF NVI_SP Forcible
nvoSpaceTemp xxx.x dF NVO_SPT
nvoUnitStatus.mode xxxx NVO_MODE
nvoUnitStatus.heat_out_p xxx.x % NVO_HPRI
nvoUnitStatus.heat_out_s xxx.x % NVO_HSEC
nvoUnitStatus.cool_out xxx.x % NVO_COOL
nvoUnitStatus.econ_out xxx.x % NVO_ECON
nvoUnitStatus.fan_out xxx % NVO_FAN
nvoUnitStatus.in_alarm xxx NVO_ALRM
nviSetPtOffset xxx.x ^F NVI_SPTO Forcible
nviOutsideTemp xxx.x dF NVI_OAT Forcible
nviOutsideRH xxxx.x % NVI_OARH Forcible
nvoEffectSetPt xxx.x dF NVO_EFSP
nvoOutsideTemp xxxx.x dF NVO_OAT
nvoOutsideRH xxx.x % NVO_OARH
nviSpaceRH xxx.x % NVI_SPRH Forcible
nviCO2 xxxxx NVI_CO2 Forcible
nvoCO2 xxxxx NVO_CO2
nvoTEMP1 xxx.x dF NVO_SAT
nvoTEMP2 xxx.x dF NVO_RAT Forcible
nviPCT1 xxx.x % NVI_RHSP
nvoPCT1 xxx.x % NVO_SPRH
nviDISCRETE1 Off/On NVI_FSD
nviDISCRETE2 No/Yes NVI_OCC
nviDISCRETE3 Off/On NVI_IAQD
nvoDISCRETE1 Off/On NVO_FSD Forcible
nvoDISCRETE2 No/Yes NVO_OCC Forcible
nvoDISCRETE3 Off/On NVO_IAQD
nciCO2Limit xxxxx NCI_CO2
nciSetPnts.occupied_cool xxx.x dF NCI_OCSP Forcible
nciSetPnts.standby_cool xxx.x dF NCI_SCSP Forcible
nciSetPnts.unoccupd_cool xxx.x dF NCI_UCSP Forcible
nciSetPnts.occupied_heat xxx.x dF NCI_OHSP Forcible
nciSetPnts.standby_heat xxx.x dF NCI_SHSP Forcible
nciSetPnts.unoccupd_heat xxx.x dF NCI_UHSP Forcible