CL-4
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE DEFAULT ENTRY
CONFIGURATION (cont)
ECON (cont)
FC.TM Free Cool PreOcc Time 1 to 9999 min 120
FC.LO Free Cool Low Temp Limit 0 to 70 dF 50
PE.EN Power Exhaust Installed Yes/No No: no FIOP
Yes: FIOP
PE.1 PE Stage1 Econo
Position
10 to 100 % 40
PE.2 PE Stage2 Econo
Position
10 to 100 % 75
EN.SW Enthalpy Switch 0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
E.TRV Economizer Travel Time 5 to 300 sec 150
E.MXB Bottom Stage Max Econo 0 to 100 % 50
E.MXM Middle Stage Max Econo 1 to 100 % 35
E.MXT Top Stage Max Econo 0 to 100 % 25
E.DBD Economizer PID
Deadband
0 to 25 % 3
EC.P Economizer PID — kP 0.0 to 99.9 sec 2.5
EC.I Economizer PID — kI 0.0 to 99.9 sec 0.1
EC.D Economizer PID — kD 0.0 to 99.9 sec 1
EC.DT Economizer PID — rate 10.0 to 180.0 sec 15
AIR.Q Air Quality Configuration
IA.CF IAQ Analog Input Config 0=No IAQ
1=Demand Ventilation
2=Econ Position Override
3=Econ Min Position Con-
trol
0: no FIOP
1: FIOP
IA.FN IAQ Analog Fan Config 0=Never
1=Only While Occupied
2=Always
0
II.CF IAQ Switch Input Config 0=No IAQ
1=DCV Normally Open
2=DCV Normally Closed
3=Override Normally
Open
4=Override Normally
Closed
0
II.FN IAQ Switch Fan Config 0=Never
1=Only While Occupied
2=Always
0
AQ.MN Econo Min IAQ Position 0 to 100 10
EC.MN Econo Minimum Position 0 to 100 30
OVR.P IAQ Override Position 0 to 100 100
OA.CF OAQ Analog Input Cfg 0=No OAQ
1=Demand Ventilation
2=Outdoor Air Lockout
0
OAQ.L OAQ Lockout Limit 0 to 5000 600
AQD.L AQ Differential Low 0 to 5000 100
AQD.H AQ Differential High 0 to 5000 700
DF.ON Fan On AQ Differential 0 to 5000 600
DF.OF Fan Off AQ Differential 0 to 5000 200
I.4M IAQ Sensor Value at 4mA 0 to 5000 0
I.20M IAQ Sensor Value at
20mA
0 to 5000 2000
O.4M OAQ Sensor Value at
4mA
0 to 5000 0
O.20M OAQ Sensor Value at
20mA
0 to 5000 2000
H.4M RH Sensor Value at 4mA 0 to 50 % 0
H.20M RH Sensor Value at
20mA
60 to 100 % 100
ALM.O
Alarm Relay
Configuration
A.SPC SPT/SPRH Sensor
Failure
Ye s / N o Ye s
A.SRT SAT/RAT Sensor Failure Yes/No Yes
A.OAT OAT Thermistor Failure Yes/No Yes
A.CS Current Sensor Failure Yes/No Yes
A.CMP Compressor Failure Yes/No Yes
A.CKT Refrigerant Circuit Failure Yes/No Yes
A.SSP SSP Transducer Failure Yes/No Yes
A.SCT SCT Thermistor Failure Yes/No Yes
A.FAN Indoor Fan Failure Yes/No Yes
A.FIL Dirty Filter Yes/No Yes
A.TST Thermostat Failure Yes/No Yes
A.ECO Economizer Failure Yes/No Yes