95
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — SERVICE TEST
MODE — TEMPERATURES
MODE — PRESSURES
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN
POINT
WRITE
STATUS
SERVICE TEST MAINTENANCE DISPLAY
TEST Field Service Test Mode On/Off Off (TEST = display only) Forcible
INDP Test Independent Outputs TESTINDP
ECON Economizer Position Test 0 to 100 % 0 S_ECONO Forcible
E.CAL Calibrate Economizer On/Off Off S_ECOCAL Forcible
PE.1 Power Exhaust 1 Test On/Off Off S_PE_1 Forcible
PE.2 Power Exhaust 2 Test On/Off Off S_PE_2 Forcible
ALRM Alarm Relay Test On/Off Off S_ALMOUT Forcible
CCH Crankcase Heat Test On/Off Off S_CCH Forcible
FANS Test Fans TESTFANS
IDF Indoor Fan Test On/Off Off S_IDF Forcible
OFC.1 Outdoor Fan 1 Test On/Off Off S_OFC_1 Forcible
OFC.2 Outdoor Fan 2 Test On/Off Off S_OFC_2 Forcible
OFC.3 Outdoor Fan 3 Test On/Off Off S_OFC_3 Forcible
COOL Test Cooling TESTCOOL
CMP.A Cool A Test On/Off Off S_COMP_A Forcible
CMP.B Cool B Test On/Off Off S_COMP_B Forcible
CMP.C Cool C Test On/Off Off S_COMP_C Forcible
OF.OV Outdoor Fan Override On/Off Off S_OFC_3 Forcible
HMZR Test Humidimizer TESTHMZR
RH1.A Reheat1 A Test On/Off Off S_RH1_A Forcible
RH1.B Reheat1 B Test On/Off Off S_RH1_B Forcible
RH1.C Reheat1 C Test On/Off Off S_RH1_C Forcible
RH2.A Reheat2 A Test On/Off Off S2_RH2_A Forcible
RH2.B Reheat2 B Test On/Off Off S2_RH2_B Forcible
RH2.C Reheat2 C Test On/Off Off S2_RH2_C Forcible
CRC Cool−>Reheat1 Valve Test On/Off Off S_CRC Forcible
RHV.A Reheat2 Valve A Test On/Off Off S_RH2_A Forcible
RHV.B Reheat2 Valve B, C Test On/Off Off S_RH2_B Forcible
HEAT Test Heating TESTHEAT
HT.1 Heat Stage 1 Test On/Off Off S_HEAT_1 Forcible
HT.2 Heat Stage 2 Test On/Off Off S_HEAT_2 Forcible
ITEM EXPANSION RANGE UNITS
CCN TABLE/
SUB-TABLE
CCN
POINT
WRITE
STATUS
STATUS DISPLAY
TEMPERATURES UINPUT
AIR.T Air Temperatures
SAT Supply Air Temperature xxx.x dF SAT_DISP
OAT Outdoor Air Temperature xxx.x dF OA_TEMP Forcible
SPT Space Temperature xxx.x dF SPACE_T Forcible
SPTO Space Temperature Offset xxx.x dF SPTO Forcible
RAT Return Air Temperature xxx.x dF RETURN_T Forcible
REF.T Refrigerant Temperatures xxx.x dF
SST.A Sat. Suction Temp A xxx.x dF SST_A
SCT.A Sat. Condenser Temp A xxx.x dF SCT_A
SST.B Sat. Suction Temp B xxx.x dF SST_B
SCT.B Sat. Condenser Temp B xxx.x dF SCT_B
SST.C Sat. Suction Temp C xxx.x dF SST_C
SCT.C Sat. Condenser Temp C xxx.x dF SCT_C
ITEM EXPANSION RANGE UNITS
CCN TABLE/
SUB-TABLE
CCN
POINT
WRITE
STATUS
STATUS DISPLAY
PRESSURES UINPUT
Refrigerant Pressures
SSP.A Suction Pressure A xxx.x psig SSP_A
SCP.A Condenser Pressure A xxx.x psig SCP_A
SSP.B Suction Pressure B xxx.x psig SSP_B
SCP.B Condenser Pressure B xxx.x psig SCP_B
SSP.C Suction Pressure C xxx.x psig SSP_C
SCP.C Condenser Pressure C xxx.x psig SCP_C