HEATING INPUT
(BTUH)
NUMBER OF
ORIFICES
40,000 2
60,000 2
90,000 3
115,000 3
130,000 3
Table 6 - Heating Inputs 208/230 VAC Models
GAS SUPPLY PRESSURE (IN. W.C.)
Natural1- Propane*l-
Max
13.0
13.0
13.0
13.0
13.0
Min Max
11.0 13.0
11.0 13.0
11.0 13.0
11.0 13.0
11.0 13.0
Natural1-
3.2-3.8
3.2-3.8
3.2-3.8
3.2-3.8
3.2-3.8
Min
4.0
4.0
4.0
4.0
4.0
MANIFOLD PRESSURE
(IN. W.C.)
Propane*l-
10.0-11.0
10.0-11.0
10.0-11.0
10.0-11.0
10.0-11.0
*When a unit is converted to propane, different size orifices must be used. See separate, natural-to-propane conversion kit instructions.
1-Based on altitudes from sea level to 2000 ff (610 m) above sea level. In U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each addi-
tional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.
Table 7 - Heating Inputs, 460 VAC Models
GAS SUPPLY PRESSURE (IN. W.C.) MANIFOLD PRESSURE (IN. W.C.)
Natural1- Propane*l- HIGH STAGE LOW STAGE
HEATING
NUMBER
INPUT, OF
HIGH STAGE
ORIFICES
(BTUH) Min Max Min Max Natural1- Propane*l- Natural1- Propane*l-
40,000 2 4.0 13.0 11.0 13.0 3.2-3.8 10.0M 1.0 1.4-2.0 4.8-6.4
60,000 3 4.0 13.0 11.0 13.0 3.2-3.8 10.0M 1.0 1.4-2.0 4.8-6.4
90,000 3 4.0 13.0 11.0 13.0 3.2-3.8 10.OM 1.0 1.4-2.0 4.8-6.4
115,000 3 4.0 13.0 11.0 13.0 3.2-3.8 10.OM 1.0 1.4-2.0 4.8-6.4
130,000 3 4.0 13.0 11.0 13.0 3.2-3.8 10.OM 1.0 1.4-2.0 4.8-6.4
*When a unit is converted to propane, different size orifices must be used. See separate, natural-to-propane conversion kit instructions.
1-Based on altitudes from sea level to 2000 ff (610 m) above sea level. In U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each addi-
tional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.