EasyManua.ls Logo

Carrier 48VG-A - Page 35

Carrier 48VG-A
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UNIT
48VG(-,N)A24060
Table 11 - Dry Coil Air Delivery* - Horizontal and Downflow Discharge - Unit 48VG-A
HEATING RISE MOTOR
RANGE SPEED COLOR
Low 1
Med-Low 3
Medium 2
Med-High 4
High
208/230 VAC Models (Cont)
WIRE EXTERNAL STATIC PRESSURE (IN. W.C.)
Blue
Pink
Red
Orange
25 - 55°F Low Stage,
25 - 55°F High Stage
Black
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM 689 597 489 352 ............
BHP 0.08 0.06 0.06 0.05 ............
Low Stage Heat Rise °F 41 48
NA NA NA NA NA NA
(°C) (23) (27)
High Stage Heat Rise °F
NA NA NA NA NA NA NA NA
(°C)
CFM 777 692 583 465 318 .........
BHP 0.09 0.10 0.10 0.11 0.12 .........
Low Stage Heat Rise °F 37 41 49
NA NA NA NA NA
(°C) (20) (23) (27)
High Stage Heat Rise °F
NA NA NA NA NA NA NA NA
(°C)
CFM 921 829 754 663 582 485 371 --
BHP 0.14 0.14 0.15 0.16 0.17 0.17 0.18 --
Low Stage Heat Rise °F 31 34 38 43 49
NA NA NA
(°C) (17) (19) (21) (24) (27)
High Stage Heat Rise °F 48 54
NA NA NA NA NA NA
(°C) (27) (30)
CFM 1229 1171 1105 1049 980 913 838 775 679 516
BHP 0.28 0.30 0.30 0.31 0.32 0.33 0.33 0.34 0.34 0.33
Low Stage Heat Rise °F NA NA 26 27 29 31 34 37 42 55
(°C) (14) (15) (16) (17) (19) (20) (23) (31)
High Stage Heat Rise °F 36 38 40 42 45 49 53
NA NA NA
(°C) (20) (21) (22) (24) (25) (27) (29)
CFM 1291 1206 1142 1081 1017 951 888 823 753 668
BHP 0.31 0.32 0.33 0.34 0.34 0.35 0.36 0.36 0.37 0.37
Low Stage Heat Rise °F NA NA 25 26 28 30 32 35 38 43
(°C) (14) (15) (16) (17) (18) (19) (21) (24)
High Stage Heat Rise °F 34 37 39 41 44 47 50 54
NA NA
(°C) (19) (20) (22) (23) (24) (26) (28) (30)
0.9
NA
NA
NA
NA
NA
NA
1
NA
NA
NA
NA
NA
NA

Table of Contents