Table 7 Output Pin and Terminal Assignments
OUTPUT PIN-
TERMINAL
NAME RATING
UNIT SIZES
024-030 034-074
J6-1
Stage 1
Compressor Relay (K1)*
24 vac
CR1
J6-2
Stage 2
Compressor Relay (K2)*
U2**
J6-3
Stage 3
Compressor Relay (K3)*
U1
J6-4
Stage 4
Compressor Relay (K4)†
Not Used
J6-5
Stage 5
Compressor Relay (K5)†
CR2
J6-6
Stage 6
Compressor Relay (K6)†
Not Used
J6-7 Economizer Open Relay (K7) EM-2 EOR
J6-8 Economizer Close Relay (K8) EM-3 ECR
J5-1 Supply Fan Relay (K9)
115 vac
IFC
J5-2 Morning Warm-Up Relay (K10) HIR
J5-3
Stage 1 Condenser
Fan Relay (K11)
OFC1/OFC2†† OFC2/OFC3 \
J5-4
Stage 2 Condenser
Fan Relay (K12)
Not Used OFC4
J5-5 External Alarm Relay (K13) R ALM
LEGEND
ALM Alarm
CR Control Relay
ECR Economizer Close Relay
EM Economizer Motor
EOR Economizer Open Relay
HIR Heat Interlock Relay
IFC Indoor (Evaporator) Fan Contactor
OFC Outdoor (Condenser) Fan Contactor
R—Alarm Relay
U—Unloader
*Circuit 1.
†Circuit 2.
**U2 is not used on 044 units.
††OFC2 is controlled by a temperature switch.
\ OFC2 on 034,044 units; OFC3 on 054-074 units.
Used on 054-074 units only.
LEGEND
CR Control Relay
J—Terminal Pin Connectors
K—Relay
Fig. 5 Relay Board