11
Install Motormaster I Controls
Only one Motormaster I
control is required per unit. The Motormaster I control must be
used in conjunction with the Accessory F Low Ambient Kit
(purchased separately). The Motormaster I device controls out-
door fan no. 1 while outdoor fans no. 2 and 3 are sequenced off
by the Accessory F Low Ambient Kit.
Accessory F Low Ambient Kit Install the Accessory F
Low Ambient Kit per instruction supplied with accessory.
Sensor Assembly Install the sensor assembly in the location
shown in Fig. 19.
Motor Mount To ensure proper fan height, replace the exist-
ing motor mount with the new motor mount provided with
accessory.
Transformer (460 and 575-v Units Only) On 460 and
575-volt units a transformer is required. The transformer is
provided with the accessory and must be field installed.
Motormaster I Control Recommended mounting location is
on the inside of the panel to the left of the control box. The
control should be mounted on the inside of the panel, verti-
cally, with leads protruding from bottom of extrusion.
To avoid damage to the refrigerant coils and electrical com-
ponents, use recommended screw sizes only. Use care
when drilling holes.
NOTE: The outdoor-air hood comes with a baffle which is not used
on 50HJQ units. Discard the baffle.
Fig. 17 Outdoor-Air Hood Details
HOOD TOP
PANEL
HOOD SIDE
PANELS (2)
LOWER
FILTER
RETAINER
FILTER SUPPORT
BRACKET
HOOD DRAIN PAN
UPPER FILTER RETAINER
LOWER FILTER
RETAINER
FILTER SUPPORT
BRACKET
NOTE: Dimensions in ( ) are in mm.
Fig. 18 Wind Baffle Details
MOTORMASTER
SENSOR
LOCATION
HAIRPIN END
Fig. 19 Motormaste I Sensor Locations
NOTES:
1. All sensors are located on the eighth
hairpin up from the bottom.
2. Field-installed tubing insulation is
required to be installed over the TXV
bulb and capillary tube for proper
operation at low ambients. Tubing
insulation is only required on the por-
tion of suction line located between
indoor and outdoor section.