8
Table 2 Electrical Data
LEGEND
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
480 v, and 600 v. If power distribution voltage to unit varies from
rated heater voltage, heater kW will vary accordingly.
†Fuse or HACR circuit breaker. This is the maximum size permissi-
ble; smaller fuse size may be used where conditions permit.
NOTES:
1. In compliance with NEC requirements for multimotor and com-
bination load equipment (refer to NEC Articles 430 and 440),
the overcurrent protective device for the unit shall be fuse or
HACR breaker. The Canadian units may be fuse or circuit
breaker.
2. MCA calculation for units with electric heaters over 50 kW =
(1.25 x IFM amps) + (1.00 x heater FLA).
UNIT
50HJQ
VOLTAGE
(3 Ph,
60 Hz)
VOLTAGE
RANGE
COMPRESSOR OUTDOOR
FAN
MOTOR
INDOOR FAN
MOTOR
POWER
EXHAUST
ELECTRIC HEAT* POWER SUPPLY
DISCONNECT
SIZING
No. 1 No. 2
Min Max RLA LRA RLA LRA Qty
FLA
(ea)
Hp FLA FLA LRA FLA kW MCA MOCP† RLA LRA
014
208/230 187 253 39.7 228 3 1.7 3.7 10.5/10.5
——
—/— —/— 65/ 65 100/100 64/ 64
387/387
39/ 45 14/19 114/122 125/150 64/ 64
72/ 82 26/34 155/168 175/175 94/107
117/135 42/56 211/200 225/225 147/167
4.6 18.8
—/— —/— 70/ 70 100/100 69/ 69
406/406
39/ 45 14/19 119/126 125/150 69/ 69
72/ 82 26/34 159/173 175/175 100/112
117/135 42/56 216/205 225/225 152/173
460 414 508 19.9 114 3 0.8 3.7 4.8
——
32 50 31
189
18 15 54 60 31
39 32 81 90 50
66 55 98 110 82
2.3 6.0
34 50 34
195
18 15 57 70 34
39 32 83 90 53
66 55 100 110 84
575 518 632 16.0 91 3 0.75 3.0 3.9
——
26 40 26
91
37 37 72 80 47
2.1 4.8
28 40 28
96
37 37 75 80 50
016
208/230 187 253 28.2 160 28.2 160 3 1.7 5 15.8/15.8
——
—/— —/— 84/ 84 110/110 89/ 89
499/48572/ 82 26/34 174/187 175/200 101/112
117/135 42/56 231/219 250/225 153/173
4.6 18.8
—/— —/— 89/ 89 110/110 94/ 94
518/50472/ 82 26/34 179/191 200/200 106/118
117/135 42/56 235/224 250/225 158/179
460 414 508 14.1 80 14.1 80 3 0.8 5 7.9
——
42 50 44
23839 32 91 100 54
66 55 108 110 85
2.3 6.0
44 50 47
24439 32 93 100 57
66 55 110 125 88
575 518 632 11.3 64 11.3 64 3 0.75 5 6.0
——
34 40 35
165
50 50 96 100 64
2.1 4.8
36 45 38
169
50 50 98 100 67
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC National Electrical Code
RLA Rated Load Amps
Fig. 8 Concentric Duct Details
Shaded area indicates block-off panels.
NOTE: Dimensions A, A and B, B are obtained
from field-supplied ceiling diffuser.