EasyManua.ls Logo

Carrier 50HS018 - Page 15

Carrier 50HS018
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 3 Electrical Data
UNIT
SIZE
50HS
V-Ph-Hz
COMPRESSOR OFM IFM
POWER SUPPLY
MOCP
RLA LRA FLA FLA MCA MAX
018 208/230-1-60 10.4 49.0 0.7 1.8 15.5 25
024 208/230-1-60 11.2 61.0 1.4 2.0 17.4 25
030
208/230-1-60 14.4 82.0 1.4 2.6 22.0 30
208/230-3-60 10.4 65.5 1.4 2.6 17.0 25
036
208/230-1-60 18.0 96.0 1.4 2.8 26.7 40
208/230-3-60 11.4 75.0 1.4 2.8 18.5 25
460-3-60 4.8 40.0 0.8 1.4 9.0 10
042
208/230-1-60 20.4 102.0 1.4 4.0 30.9 50
208/230-3-60 14.0 91.0 1.4 4.0 22.9 30
460-3-60 6.4 42.0 0.8 2.0 10.8 15
048
208/230-1-60* 24.4 140.0 2.1 5.0 40.1 60
208/230-1-60† 26.4 129.0 2.1 5.0 40.1 60
208/230-3-60* 14.1 105.0 2.1 5.0 25.9 35
208/230-3-60† 15.0 99.0 2.1 5.0 25.9 40
460-3-60* 7.1 55.0 1.1 2.3 13.7 15
460-3-60† 8.2 49.5 1.1 2.3 13.7 20
060
208/230-1-60* 28.9 165.0 2.1 6.2 48.4 60
208/230-1-60† 32.1 169.0 2.1 6.2 48.4 60
208/230-3-60* 16.0 125.0 2.1 6.2 32.4 40
208/230-3-60† 19.3 123.0 2.1 6.2 32.4 50
460-3-60* 8.0 66.0 1.1 3.2 16.8 20
460-3-60† 10.0 62.0 1.1 3.2 16.8 25
LEGEND
CSA Canadian Standards Association
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor-Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
(fuses or HACR-type circuit breaker)
NEC National Electrical Code
OFM Outdoor-Fan Motor
RLA Rated Load Amps
*Carrier Scroll Compressor.
†Copeland Scroll Compressor.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
The CSA units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%.
Use the following formula to determine the per-
cent of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more
than 2%, contact your local electric utility company immediately.
15

Related product manuals