16
Performance data (cont)
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE -1020
HEATING EXTENDED PERFORMANCE TABLE 3060
See Legend and Notes on page 17. *At 75°F entering dry bulbTennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
50 JX060 (5 TONS)
Temp (F)
Air Ent
Outdoor Coil
(Edb)
Indoor Entering AirCFM/BF
1750/0.07 2000/0.12 2250/0.15
Indoor Entering AirEwb (F)
72 67 63* 62 72 67 63* 62 72 67 63* 62
85
TC 67.9 61.8 56.5 55.5 68.9 63.3 57.9 57.2 69.6 64.4 59.1 59.0
SHC 35.1 44.4 42.2 52.5 36.8 47.7 45.2 56.4 38.4 50.7 48.2 59.0
kW 5.25 5.22 5.16 5.15 5.27 5.22 5.19 5.18 5.28 5.22 5.22 5.22
95
TC 65.3 59.0 53.4 52.5 66.5 59.8 54.7 54.3 67.3 61.1 55.8 56.3
SHC 34.3 43.3 40.8 50.9 36.2 46.1 43.8 54.3 38.0 49.5 46.7 56.3
kW 5.78 5.74 5.63 5.61 5.78 5.77 5.66 5.66 5.79 5.76 5.69 5.70
105
TC 62.8 55.2 50.5 49.5 64.0 57.1 51.5 51.6 64.1 57.5 52.5 53.7
SHC 33.6 41.5 39.7 49.4 35.6 45.3 42.4 51.6 36.9 47.9 45.3 53.7
kW 6.34 6.27 6.21 6.14 6.36 6.32 6.18 6.19 6.35 6.35 6.21 6.24
115
TC 58.7 52.3 46.9 47.1 59.9 53.1 48.1 49.0 60.7 54.1 49.4 50.9
SHC 31.8 40.6 38.0 47.1 33.9 43.4 40.9 49.0 35.8 46.5 44.3 50.9
kW 6.94 6.78 6.72 6.64 6.95 6.90 6.75 6.77 6.96 6.94 6.69 6.82
50 JX060 (5 TONS)
Temp (F) Indoor Air Cfm (std) Air Temperature Entering Outdoor Coil (F db at 70% rh)
Air Ent Indoor Coil -10 0 10 17 20
60
1750
TC
22.7
21.0 27.8 25.6 33.3 30.5 36.6 33.4 39.4 35.7
kW
3.82 4.08 4.15
4.21 4.27
2000
TC
23.2
21.4 28.5 26.3 33.5 30.9 36.8 33.6 40.0 36.3
kW
3.81 3.94 4.12 4.17 4.21
2250
TC
23.4
21.6 28.6 26.3 33.8 31.1 37.2 33.9 40.5 36.7
kW
3.79 3.92 4.04 4.10 4.15
70
1750
TC
21.1
19.5 26.4 24.3 32.8 30.1 35.8 32.6 38.8 35.2
kW
4.02 4.27 4.48
4.55 4.63
2000
TC
21.3
19.7 27.3 25.1 32.9 30.2 36.0 32.8 39.1 35.5
kW
4.01 4.26 4.42 4.49 4.57
2250
TC
21.5
19.9 28.4 26.1 33.1 30.4 36.2 33.0 39.3 35.7
kW
4.00 4.21 4.49 4.49 4.50
80
1750
TC
18.1
16.7 21.1 19.4 32.2 29.5 35.1 32.0 38.0 34.4
kW
4.12 4.48 4.83
4.94 5.05
2000
TC
18.3
16.9 22.7 20.9 31.9 29.3 34.9 31.8 38.0 34.4
kW
4.11 4.47 4.77 4.88 4.98
2250
TC
18.5
17.1 25.4 23.4 30.8 28.3 35.1 32.0 39.3 35.7
kW
4.11 4.48 4.69 4.82 4.95
50 JX060 (5 TONS)
Temp (F) Indoor Air Cfm (std) Air Temperature Entering Outdoor Coil (F db at 70% rh)
Air Ent Indoor Coil 30 40 47 50 60
60
1750
TC
46.1
40.4 52.8 52.8 57.7 57.7 59.4 59.4 64.8 64.8
kW
4.39 4.57 4.62
4.66 4.79
2000
TC
46.7
40.9 53.0 53.0 57.5 57.5 59.1 59.1 64.1 64.1
kW
4.35 4.41 4.50 4.53 4.64
2250
TC
46.7
40.9 52.9 52.9 57.3 57.3 58.6 58.6 63.3 63.3
kW
4.27 4.32 4.41 4.43 4.53
70
1750
TC
45.3
39.7 52.5 52.5 57.2 57.2 59.3 59.3 65.0 65.0
kW
4.81 5.04 5.05
5.09 5.24
2000
TC
45.8
40.1 52.5 52.5 57.3 57.3 59.3 59.3 64.5 64.5
kW
4.76 4.93 4.92 4.96 5.08
2250
TC
45.8
40.2 52.3 52.3 57.4 57.4 59.1 59.1 64.1 64.1
kW
4.65 4.82 4.82 4.85 4.96
80
1750
TC
44.2
38.8 51.2 51.2 56.1 56.1 58.6 58.6 65.0 65.0
kW
5.21 5.51 5.56
5.57 5.73
2000
TC
44.2
38.8 52.1 52.1 56.5 56.5 58.8 58.8 64.9 64.9
kW
5.09 5.39 5.40 5.43 5.57
2250
TC
44.3
38.8 51.6 51.6 56.7 56.7 58.9 58.9 64.7 64.7
kW
4.87 5.32 5.29 5.32 5.45