Table 5—Wet Coil Air Delivery-English
Unit 50JZ 024-048*
UNIT MOTOR SPEED
EXTERNAL STATIC PRESSURE (IN. WG)
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
024
Low
Watts 303 305 303 300 ———————
Cfm969879785687———————
High
Watts ————435428428422———
Cfm ————963833758676———
030
Low
Watts 814 853 889 921 954 1002 ————
Cfm 1189 1115 1041 971 903 833 ————
High
Watts ———————700683688755
Cfm ———————1223 1142 1075 1058
036
Low
Watts 552 540 529 523 514 480 —————
Cfm 1296 1237 1167 1097 1029 952 —————
High
Watts —————7827657367217801002
Cfm —————1467 1398 1321 1237 1165 1137
048
Low
Watts 692 686 678 664 652 664 736 ————
Cfm 1571 1509 1444 1370 1295 1240 1237 ————
High
Watts 1112 930 856 834 825 811 793
Cfm 1693 1670 1601 1521 1447 1378 1294
* Air delivery values are based on operating voltage of 400-v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drop (see Tables 5 and
6) to obtain static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh (165 L/s for each 3.5 kW) of rated cooling capacity. Evaporator coil frosting
may occur at airflows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
Table 6—Wet Coil Air Delivery-SI
Unit 50JZ 024-048*
UNIT MOTOR SPEED
EXTERNAL STATIC PRESSURE (PA)
0 25 50 75 100 125 150 175 200 225 250
024
Low
Watts 303 305 303 300
L/s 458 415 371 324
High
Watts 435 428 428 422
L/s 455 393 358 319
030
Low
Watts 814 853 889 921 954 1002
L/s 561 526 491 458 426 393
High
Watts 700 683 688 755
L/s 577 539 508 499
036
Low
Watts 552 540 529 523 514 480
L/s 612 584 551 518 486 449
High
Watts 782 765 736 721 780 1002
L/s 693 660 624 584 550 536
048
Low
Watts 692 686 678 664 652 664 736
L/s 741 712 681 647 611 585 584
High
Watts 1112 930 856 834 825 811 793
L/s 799 788 756 718 683 650 611
* Air delivery values are based on operating voltage of 400-v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drop (see Tables 5 and
6) to obtain static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 165 L/s for each 3.5 kW of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.