EasyManua.ls Logo

Carrier 50JZ - Page 26

Carrier 50JZ
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fig. 26—Defrost Thermostat
C99029
FEEDER TUBE
STUB TUBE
DEFROST
THERMOSTAT
HEAT PUMP WITH PURON—QUICK REFERENCE GUIDE
Puron refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are
designed to operate with Puron. Puron refrigerant cylinders are rose colored.
Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright position.
Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow.
Recovery cylinder service pressure rating must be 400 psig (2758 kpa). DOT 4BA400 or DOT BW400.
Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.
Manifold sets should be 750 psig (5171 kpa) high-side and 200 psig (1379 kpa) low-side with 520 psig (3585 kpa) low-side retard.
Use hoses with 750 psig (5171 kpa) service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
Puron, as with other HFCs, is only compatible with POE oils.
Vacuum pumps will not remove moisture from oil.
Only use factory specified liquid-line filter driers with rated working pressures no less than 600 psig (4137 kpa).
Do not install a suction-line filter drier in liquid line.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials.
Wrap all filter driers and service valves with wet cloth when brazing.
A Puron liquid-line filter drier is required on every unit.
Do not use an R-22 TXV.
Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.
Do not vent Puron into the atmosphere.
Observe all warnings, cautions, and bold text.
Do not leave Puron suction line driers in place for more than 72 hrs.
26

Other manuals for Carrier 50JZ

Related product manuals