UNIT ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT
IN. [MM]
"A"
CENTER OF GRAVITY
IN. [MM]
lb kg X Y Z
50JZ024 208/230-1-60 299 135.6 35.02 [889.5] 19.0 [482.6] 18.3 [463.6] 16.0 [406.4]
50JZ030 208/230-1-60,208/230-3-60 320 145.2 37.02 [940.3] 20.0 [508.0] 19.3 [489.0] 17.6 [447.0]
50JZ036 208/230-1-60,208/230-3-60, 460-3-60 328 148.8 37.02 [940.3] 20.0 [508] 19.0 [482.6] 16.5 [419.1]
Fig. 2—50JZ024-036 Unit Dimensions
C00064
REQ’D CLEARANCES FOR OPERATION AND SERVICING. IN.(MM)
EVAPORATOR COIL ACCESS SIDE ............. 36(914)
POWER ENTRY SIDE (EXCEPT FOR NEC REQUIREMENTS) . . 36 (914)
UNIT TOP..........................48(1219)
SIDE OPPOSITE DUCTS ...................36(914)
DUCT PANEL .......................12(304.8)*
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12 IN. (304.8 MM) FROM
WALL SYSTEM, THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED.
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. IN.(MM)
TOP OF UNIT .......................14(355.6)
DUCT SIDE OF UNIT.....................2(50.8)
SIDE OPPOSITE DUCTS ..................14(355.6)
BOTTOM OF UNIT.....................0.50 (12.7)
ELECTRIC HEAT PANEL ..................36(914.4)
NEC REQ’D CLEARANCES. IN.(MM)
BETWEEN UNITS, POWER ENTRY SIDE
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE
UNIT AND BLOCK OF CONCRETE WALLS AND OTHER
GROUNDED SURFACES, CONTROL BOX SIDE
..........42(1066.8)
. . 36 (914)
.......42(1066.8)
LEGEND
CG - CENTER OF GRAVITY
COND - CONDENSER
EVAP - EVAPORATOR
NEC - NATIONAL ELECTRICAL CODE
REQ'D - REQUIRED
NOTE: DIMENSIONS ARE IN IN. (MM)
44.5 [1.75]