13
Table 4—Wet Coil Air Delivery* — Horizontal Discharge
(Deduct 10% for 208--Volt Operation)
230 VOLT HORIZONTAL DISCHARGE
UNIT
SIZE
MOTOR
SPEED
AIR
DELIVERY
EXTERNAL STATIC PRESSURE (IN.WG)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
024
Low
Watts 311 309 304 301 286 — — — — —
CFM 935 885 820 757 686 — — — — —
Med
Watts — — — — 379 357 357 345 327 —
CFM — — — — 957 868 769 647 365 —
High
Watts — — — — — — 447 435 421 —
CFM — — — — — — 970 853 712 —
030
Low
Watts 311 309 304 301 — — — — — —
CFM 935 885 820 757 — — — — — —
Med
Watts 411 405 398 390 379 357 357 — — —
CFM 1195 1155 1100 1028 957 868 769 — — —
High
Watts — — — — 477 467 447 435 — —
CFM — — — — 1185 1088 970 853 — —
036
Low
Watts 437 433 424 417 403 391 379 362 — —
CFM 1353 1318 1283 1235 1187 1123 1059 975 — —
Med
Watts — — — 531 516 496 478 459 435 —
CFM — — — 1489 1437 1362 1289 1208 1099 —
High
Watts — — — — — — — 629 602 —
CFM — — — — — — — 1470 1357 —
042
Low
Watts 625 606 586 571 550 534 509 483 457 —
CFM 1539 1496 1466 1437 1387 1330 1264 1183 1093 —
Med
Watts — 741 715 694 669 645 610 573 544 —
CFM — 1738 1698 1653 1604 1538 1457 1362 1271 —
High
Watts — — — — — 798 772 738 700 —
CFM — — — — — 1720 1648 1540 1414 —
048
Low
Watts 627 617 607 584 567 548 528 503 — —
CFM 1550 1530 1493 1461 1414 1361 1320 1250 — —
Med
Watts 771 755 734 711 690 665 639 607 572 —
CFM 1798 1771 1734 1687 1645 1595 1530 1449 1355 —
High
Watts — — 908 887 858 827 804 767 748 —
CFM — — 2000 1994 1876 1811 1735 1647 1555 —
060
Low
Watts 786 769 754 736 722 705 684 658 — —
CFM 2027 1960 1901 1821 1759 1693 1616 1513 — —
Med
Watts 873 849 833 815 798 782 763 748 — —
CFM 2095 2026 1962 1887 1817 1748 1679 1583 — —
High
Watts 1012 993 981 963 948 927 904 886 — —
CFM 2184 2109 2036 1963 1886 1812 1729 1647 — —
*Air delivery va lues ar e based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct f ilter and electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occuratair-
flows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
50SD