EasyManua.ls Logo

Carrier 58SC - User Manual

Carrier 58SC
8 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
58SS/DH
Induced-Combustion
Gas-Fired
Furnaces
HEATING*
COOLING
Application
Data
Installation
Guidelines
Procedures
INTRODUCTION
The
desire
to
conserve
energy
has
created
greater
use
of
insulation,
improved
vapor
barriers,
weather
stripping,
etc.
Homes
are
now
tighter,
resulting
in
less
natural
air
infiltration
and
inefficient
furnace
oper¬
ation.
The
condition
is
further
affected
by
the
growing
use
of
kitchen
and
bathroom
exhausts
and
even
fireplaces.
Field
studies
indicate
that
combustion
air
starvation,
particularly
in
closet
installations,
points
to
a
need
for
positive
furnace
air
supply,
plus
new
guidelines
for
to¬
day’s
furnace
applications.
A
WARNING
These
instructions
cover
minimum
combustion
air
requirements
and
venting
practices.
They
also
reflect
current
conditions
found
in
the
field,
and
conform
to
existing
national
standards,
and
safety
codes.
In
some
instances,
these
instructions
exceed
certain
local
codes
and
ordinances,
especially
those
that
may
not
have
kept
pace
with
changing
construction
practices.
Carrier
requires
these
standard
pro¬
cedures
as
a
minimum
for
safe
installation.
A
CAUTION
Do
not
block
openings
in
front
of
furnace
or
on
furnace
top
along
side
vent
pipe.
These
openings
pro¬
vide
air
for
combustion
and
ventilation.
Never
store
anything
on
or
in
contact
with
furnace,
such
as:
aerosol
cans,
rags,
brooms
and
mops,
cleaning
tools
and
aids,
powders,
bleaches,
waxes,
plastic
items,
gasoline,
kerosene,
lighter
fluids,
cleaning
fluids,
thinners,
painting
compounds
or
paper
products.
Installation
Procedures
These
recommendations
apply
to
the
installation
and
operation
of
gas
furnaces
and
piping
systems
for
natural
or
LP
(propane)
gases.
Use
these
procedures
in
conjunction
with
your
specific
furnace
installation
instructions.
Refer
also
to
your
gas
supplier
regulations
and
local
building,
heating,
plumbing
and
other
codes
for
your
installation
area.
Portions
of
the
following
have
been
adopted
in
part
from
the
National
Fuel
Gas
Code
(NFPA
No.
54-1984
or
ANSI
Z223.1-1984)
copyrighted
by
the
National
Fire
Protection
Association
and
American
Gas
Association.
For
further
details,
consult
this
publication
or
current
edition
available
from
NFPA,
Batterymarch
Park,
Quincy,
MA
02269,
or
American
Gas
Association,
1515
Wilson
Boulevard,
Arlington,
VA
22209.
CONTENTS
Page
INSPECTION.
1
FURNACE
LOCATION
COMBUSTION/
VENTILATION
AIR.
1
GAS
PIPING
.
3
VENTING.
4
ELECTRICAL.
5
START-UP,
ADJUSTMENT
AND
SAFETY
CHECK.
5
FURNACE
LOCATION
WITH
RESPECT
TO
COOLING
EQUIPMENT.
7
SPECIAL
LOCATIONS.
7
APPENDIX
VENTING
REPLACEMENT
INSTALLATIONS
.
7
INSPECTION
Check
available
power
supply
to
be
sure
it
meets
speci¬
fications
on
wiring
diagram
and
all
motors
in
furnace.
Check
available
gas
supply
to
see
that
it
conforms
to
gas
specifications
on
AGA
rating
plate.
FURNACE
LOCATION
COMBUSTION/VENTILATION
AIR
Locate
furnace
close
to
chimney
and
as
near
to
the
center
of
the
air
distribution
system
as
possible.
Install
furnace
as
level
as
possible.
Provide
ample
space
for
servicing
and
cleaning.
Always
comply
with
minimum
fire
protection
clearances
shown
on
unit
rating
plate.
Do
not
install
directly
on
carpeting,
tile
or
any
combustible
material
other
than
wood
flooring.
Accessory
com¬
bustible
floor
base
is
available
from
your
dealer
when
required.
The
relief-air
supply
for
the
draft
safeguard
duct
(draft
hood)
must
be
in
the
same
atmospheric
pressure
zone
as
the
combustion-air
inlet
supply
to
the
furnace.
When
a
furnace
is
installed
so
that
the
supply
ducts
carry
air
to
areas
outside
the
space
containing
the
furnace,
the
return
air
must
also
be
handled
by
duct(s)
sealed
to
the
furnace
casing
and
terminating
outside
the
furnace
location
area.
All
fuel-burning
furnaces
must
be
supplied
with
air
that
enters
the
combustion
process
and
then
is
vented
to
the
outdoors.
Sufficient
air
must
enter
the
space
contain¬
ing
the
furnace
to
replace
the
amount
drawn
up
the
vent
stack.
Replacement
air
must
be
provided
by
means
of
ducts
from
the
outside
to
the
furnace
area
or
heated
space.
Under
all
conditions,
enough
air
must
be
provided
to
ensure
there
will
be
no
negative
pressure
condition
Manufacturer
reserves
the
right
to
discontinue,
or
change
at
any
time,
specifications
or
designs
without
notice
and
without
incurring
obligations.
Book
l
l
PC
101
Catalog
No
515-808
Printed
in
U
S
A
Form
58D.S-2XA
Pg
1
6-85
Replaces:
58D.S-1XA
Tab
|6a
Question and Answer IconNeed help?

Do you have a question about the Carrier 58SC and is the answer not in the manual?

Overview

The Carrier 58SS/DH Induced-Combustion Gas-Fired Furnaces are designed for residential and light commercial heating applications, utilizing induced combustion to enhance efficiency and safety. These furnaces are engineered to address modern construction practices, which often result in tighter homes with reduced natural air infiltration, necessitating positive furnace air supply and updated installation guidelines.

Function Description:

These furnaces operate by drawing combustion air into a sealed combustion chamber using an induced-draft blower. This ensures a consistent and controlled air supply for combustion, independent of ambient room air pressure. The combustion gases are then safely vented to the outdoors. The induced-draft system helps maintain a negative pressure within the vent, preventing spillage of combustion products into the living space. A key safety feature is the draft safeguard switch, which monitors vent pressure and will shut down the furnace if a positive pressure condition (indicating a blocked flue) is detected, preventing unsafe operation. The furnace also incorporates a limit control safety check, which monitors the furnace temperature and energizes the circulating-air blower motor if the furnace overheats, or shuts off the combustion control system if necessary. A flow-sensing switch further ensures the proper operation of the draft inducer blower.

Important Technical Specifications:

  • Venting Category: Category I, meaning it's a nonpositive venting system with static pressure in the vent less than atmospheric pressure and stack gas temperature at least 140 degrees F above the dew point.
  • Combustion Air Requirements: Approximately 20 cubic feet of air for every 1000 Btuh of gas consumed. For a 100,000-Btuh furnace, this translates to 2000 cubic feet of air per hour or 33 cubic feet per minute.
  • Gas Pipe Sizing: Refer to Table 1 in the manual for maximum capacity of gas pipe based on nominal iron pipe size, internal diameter, and length of pipe. For example, a 1/2-inch pipe (0.622 in. ID) can handle 175 cu ft/hr at 10 ft, while a 1 1/2-inch pipe (1.610 in. ID) can handle 2100 cu ft/hr at 10 ft. These figures are based on a gas pressure of 0.5 psig or less and a pressure drop of 0.5 in. wg.
  • Vent Pipe Clearance: Single-wall vent pipes require 6 inches of clearance from combustible materials, while Type-B1 (double-wall) vents require 1 inch.
  • Vent Pipe Slope: All horizontal runs of vent pipe must maintain a minimum upward slope of 1/4 inch per linear foot.
  • Chimney/Gas Vent Height: Must extend at least 5 feet above the highest connected draft hood, 3 feet higher than the point of emergence through the roof, and at least 2 feet higher than any object within a 10-foot radius.
  • Electrical Requirements: Voltage, frequency, and phase must match the furnace rating plate specifications. The service provided by the utility must be sufficient for the additional load.
  • Grounding: The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/NFPA 70-1984, and local codes. Gas piping should not be used as an electrical ground.
  • High Altitude Derating: For altitudes over 2000 ft, ratings are reduced by 4% for each 1000 ft above sea level, requiring main burner orifice changes.

Usage Features:

  • Installation Flexibility: Can be installed in confined spaces (e.g., closets) or unconfined spaces (e.g., basements, large equipment rooms). Specific guidelines are provided for combustion/ventilation air supply depending on the space type and whether air is drawn from inside the building or directly from outdoors.
  • Air Supply for Confined Spaces (Inside Building): Requires two permanent openings (one within 12 inches of the top, one within 12 inches of the bottom) with a minimum free area of 1 sq in. per 1000 Btuh of total input rating (not less than 100 sq inches). If the building is unusually tight, an additional permanent opening communicating directly with outdoors (1 sq in. per 5000 Btuh) is required, with ducts connected to the cold air return of the heating system.
  • Air Supply for Confined Spaces (Outdoors): Requires two permanent openings (one within 12 inches of the top, one within 12 inches of the bottom) communicating directly or by ducts with outdoors. Horizontal ducts require 1 sq in. per 2000 Btuh, while vertical ducts/openings with louvers/grilles require 1 sq in. per 4000 Btuh.
  • Air Supply for Unconfined Spaces: If the unconfined space is in a tightly constructed building, a permanent opening (or openings) with a total free area of not less than 1 sq in. per 5000 Btuh of total input rating for all equipment must be provided from outdoors.
  • Gas Piping: Requires a sediment trap in the riser leading to the furnace to collect dirt or condensate. An accessible manual shutoff valve must be installed upstream of the furnace gas controls and within 6 ft of the furnace. A 1/8-in. NPT plugged tapping for test gage connection is required upstream of the gas supply connection.
  • Intermittent Ignition System: Features a reliable ignition system. The pilot flame can be adjusted to control the burner-on time delay.
  • Temperature Rise Adjustment: Blower speed can be adjusted to control the air temperature rise across the furnace, ensuring it stays within the specified range on the unit rating plate.
  • Common Venting: Can be connected to a common chimney or listed Type-B1 gas vent with other listed gas-fired appliances, provided the vent system remains at negative pressure during normal operation. Flow charts are provided for replacement installations on existing chimneys.
  • Cooling Equipment Integration: Cooling coils must be installed parallel with or downstream of the furnace to prevent condensation in the heating element. Dampers or other means must prevent chilled air from entering the unit when heating, and vice versa.
  • Special Locations: Specific guidelines for installation in residential garages (burners/ignition source 18 inches above floor, protected from physical damage) and public garages/airplane hangars (according to National Fire Protection Association requirements).

Maintenance Features:

  • Accessibility: Ample space should be provided around the furnace for servicing and cleaning.
  • Gas Leak Check: After all gas connections are made, lines must be purged and checked for leakage using a soap-and-water solution. Never use matches, candles, flame, or other ignition sources.
  • Electrical Connection Check: All electrical connections (factory and field) should be checked for tightness, especially after the unit has reached operating temperatures or if aluminum conductors are used.
  • Combustion Air Quality: Combustion air must not be contaminated by halogens (fluorides, chlorides, bromides, iodides) found in aerosols, detergents, bleaches, cleaning solvents, salts, and air fresheners, as these are highly corrosive to gas-fired furnaces. If contaminants are present, outside air must be ducted separately to the furnace room.
  • Louver and Grille Maintenance: Louvers and grilles used for combustion and dilution air must be constructed so they cannot be closed, ensuring continuous air supply. Screens used must not be smaller than 1/4-inch mesh.
  • Sediment Trap Cleaning: The sediment trap in the gas piping should be periodically checked and cleaned to prevent dirt or condensate from reaching the gas controls.
  • Draft Safeguard Switch Reset: In case of a blocked flue condition and subsequent shutdown, the draft safeguard switch must be reset after the vent pipe is reconnected and the system has cooled.
  • Vent System Inspection: The vent system should always be examined prior to installation of the furnace, and regularly inspected for restrictions or damage.
  • Return Air Duct Integrity: All duct connections to the furnace must be airtight to avoid negative pressure conditions in the room, which can affect combustion. Return air should not be taken from the room unless an equal or greater amount of air is supplied to the room.

Carrier 58SC Specifications

General IconGeneral
BrandCarrier
Model58SC
CategoryFurnace
LanguageEnglish

Related product manuals