APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
BMS Protocol
Low Load
Date/Time Configuration
Navigation: MAIN MENU SYSTEM CONFIGURATION MENU DATE/TIME CONFIGURATION
Fig. E — Date/Time Configuration Menu
CCN TABLE NAME: CONNECT
PIC6 PATH: Main Menu Configuration Menu  BMS Protocol
LINE PIC6 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1
Port J8 Option
0=None, 1=BACnet MS/TP,
2=Modbus RTU
j8_opt 0 to 2 0 RW
Modbus Configuration
2
Modbus TCP Enable mip_opt Disable/Enable Disable RW
3
Modbus TCP Port Number port_nbr 0 to 1024 502 RW
4
Modbus Server UID ser_UID 1 to 255 1 RW
5
Modbus Metric Unit metric No/Yes No RW
6
Modbus RTU Parity Option
0=No, 1=Odd, 2=Even, 3=Low, 4=High
parity 0 to 4 0 RW
7
Modbus RTU Stop Bit
1= 1 Bit, 2= 2 Bits
stop_bit 1 to 2 2 RW
8
Modbus RTU Baudrate
0=9600, 1=19200, 2=38400
baudrate 0 to 2 0 RW
9
Modbus Litte Endian swap_b No/Yes No RW
10
Modbus Real Type real_typ No/Yes No RW
BACnet Configuration
11
BACnet/IP Enable bacena Disable/Enable Disable RW
12
BACnet Metric Unit bacunit No/Yes No RW
13
BACnet Network network 1 to 9999 1600 RW
14
BACnet Identifier bac_id 0 to 9999999 1600001 RW
15
BACnet Schedule Enable bacschen Disable/Enable Disable RW
16
MS/TP Mac address mstpaddr 1 to 127 1 RW
17
MS/TP Baud rate
0=9600, 1=19200, 2=38400, 3=57600,
4=76800, 5=115200
mstpbaud 0 to 5 2 RW
18
MS/TP Max Master maxmastr 0 to 127 3 RW
19
MS/TP Max Info Frames maxinfof 1 to 255 5 RW
CCN TABLE NAME: CONNECT
PIC6 PATH: Main Menu Configuration Menu  Low Load
LINE PIC6 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1
Dynamic Demand Limit lqbp_opt DISABLE/ENABLE DISABLE RW
2
LCW at Selection Point sel_lcw 32 to 86 45 RW
3
LCDW at Selection Point sel_lcdw 59 to 113 90 RW