Fig. 13 — Machine Rigging Guide
*The 11th character of the chiller model number indicates the compressor type.
COMPRESSOR
TYPE*
HEAT
EXCHANGER
CODE
MAXIMUM WEIGHT
VESSEL
LENGTH
DIM.
“A”
CHAIN LENGTH
DIM.
“E”
DIM.
“F”
“B” “C” “D”
lb ft ft-in. ft-in. ft-in. ft-in. ft-in. ft-in.
P
A1-A6 15,582 12’ 6’ -7” 12-5 11-6 11-10 3-6 1-6
B1-B6 16,391 14’ 7-5 13-0 12-0 12-4 3-6 1-6
Q
30-32 17,962 12 6-10 13-5 13-0 12-5 3-11 3-8
35-37 19,501 14 7-8 13
-10 13-5 12-10 3-11 3-8
40-42, 4D 21,032 12 6-10 13-6 12-8 12-3 4-1 3-11
45-47, 4E 22,468 14 7-8 13-11 13-2 12-8 4-1 3-11
50-52 23,856 12 6-10 13-10 12-7 12-9 4-0 4-4
55-57 25,642 14 7-8 14-4 13-1 13-1 4-0 4-4
R
30-32 19,187 12 6-10 13-5 13-0 12-5 3-11 3-8
35-37 20,589 14 7-8 13-10 13-5 12-10 3-11 3-8
40-42 23,928 12 6-10 13-6 12-8 12-3 4
-1 3-11
45-47 25,167 14 7-8 13-11 13-2 12-8 4-1 3-11
50-52 26,950 12 6-10 13-10 12-7 12-9 4-0 4-4
55-57 28,479 14 7-8 14-4 13-1 13-1 4-0 4-4
COMPRESSOR
TYPE*
HEAT
EXCHANGER
CODE
MAXIMUM WEIGHT
VESSEL
LENGTH
DIM.
“A”
CHAIN LENGTH
DIM.
“E”
DIM.
“F”
“B” “C” “D”
kg mm mm mm mm mm mm mm
P
A1-A6 7 068 3658 2007 3785 3505 3607 1067 457
B1-B6 7 435 4267 2261 3962 3658 3759 1067 457
Q
30-32 8 147 3658 2083 4089 3962 3785 1194 1118
35-37 8 846 4267 2337 4216 4089 3912 1194 1118
40-42, 4D 9 540 3658 2083 4115 3861 3734 1245 1194
45-47, 4E 10 191 4267 2337 4242 4013 3861 1245 1194
50-52 10 821 3658 2083 4216 3835 3886 1219 1321
55-57 11 631 4267 2337 4369 3988 3988 1219 1321
R
30-32 8 703 3658 2083 4089 3962 3785 1194 1118
35-37 9 339 4267 2337 4216 4089 3912 1194 1118
40-42 10 854 3658 2083 4115 3861 3734 1245 1194
45-47 11 416 4267 2337 4242 4013 3861 1245 1194
50-52 12 224 3658 2083 4216 3835 3886 1219 1321
55-57 12 918 4267 2337 4369 3988 3988 1219 1321