EasyManua.ls Logo

Carrier Base Series - User Manual

Carrier Base Series
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
24ABB3
Baset Series Air Conditioner with Puronr
1 --- 1 / 2 t o 5 N o m i n a l To n s
Single and Three Phase
Wiring Diagrams
NOTES:
1. Symbols are electrical representation only.
2. Compressor and fan motor furnished with inherent thermal protection.
3. To be wired in accordance with National Electric N.E.C. and local codes.
4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.
5. Use copper conductors only. Use conductors suitable for at least 75ºC (167ºF).
6. Connection for typical cooling only thermostat. For other arrangements see installation instructions.
7. If indoor section has a transformer with a grounded secondary, connect the grounded
side to the BRN/YEL lead.
8. When start relay and start capacitor are installed, start thermistor is not used.
9. CH not used on all units.
10. If any of the original wire, as supplied must be replaced, use the same or equivalent wire.
11. Check all electrical connections inside control box for tightness.
12. Do not attempt to operate unit until service valves have been opened.
13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize
between high and low side before starting.
14. Wire not present if HPS, LPS or CTD are used.
CONNECTION DIAGRAM
1. Compressor damage may occur if system is over charged.
2. This unit is factory charged with R-410A in accordance with
the amount shown on the rating plate. The charge is
adequate for most systems using matched coils and tubing
not over 15 feet long. Check refrigerant charge for maximum
efficiency. See Product Data Literature for required Indoor
air Flow Rates and for use of line lengths over 15 feet.
3. Relieve pressure and recover all refrigerant before system
repair or final disposal. Use all service ports and open all
flow-control devices, including solenoid valves.
4. Never vent refrigerant to atmosphere. Use approved
recovery equipment.
330440-101 REV. F
* MAY BE FACTORY INSTALLED
LEGEND
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONT
CAP
*CH
*CHS
COMP
*CTD
*DTS
*HPS
IFR
*LLS
*LPS
OFM
*SC
*SR
*ST
CONTACTOR
CAPACITOR (DUAL RUN)
CRANKCASE HEATER
CRANKCASE HEATER SWITCH
COMPRESSOR
COMPRESSOR TIME DELAY
DISCHARGE TEMP SWITCH
HIGH PRESSURE SWITCH
INDOOR FAN RELAY
LIQ LINE SOLENOID VALVE
LOW PRESSURE SWITCH
OUTDOOR FAN MOTOR
START CAPICATOR
START RELAY
START THERMISTOR
CAUTION
BLK
or
RED
*CH
RED or BLK
BLK
YEL
YEL
COMP
BLK
BLU
CA
P
YEL
BLU
BLU
YEL
*ST
BRN
*SR
OFM
BRN
BRN/YEL
BLK
BLK
208/230 1Ø
POWER
SUPPLY
GND
EQUIP
+
t
L1
L2
H
C
F
YEL
VIO
YEL/ BLU
(NOTE #14)
(NOTE #9)
(NOTE #8)
INDOOR BLOWER MOTOR
EXTERNAL
POWER
SUPPLY
24 V
(NOTE #3)
INDOOR THERMOSTAT (NOTE #6)
R
G
Y
*LLS
BLK
BLK
1
2
5
S
C
R
C
R
*SC
*CHS
BLK
*LPS
*DTS
BLK
BLK
*CTD
LOGIC
T1 T3
T2
YEL/PNK
BLU/PNK
BLK
YEL/ BLU
BRN/YEL
*HPS
YEL/PNK
BLU/PNK
CONT
11
21
23
23
SCHEMATIC DIAGRAM (LADDER FORM)
L1
*SR
*SC
H
COMP
*ST
C
F
CAP
OFM
L2
5
2
1
*LPS
* CTD
*DTS
*LLS
IFR
THERMOSTAT
INDOOR
Y
G
R
C
R
EXTERNAL POWER SUPPLY 24 V
(NOTE #14)
+
t
LOGIC
T1 T3
T2
CONT
S
C
R
*HPS
EQUIP
GND
*CH
*CHS
11
21
CONT
CONT
23
23
COOLING ONLY
CHARGING PROCEDURE
1. Only use sub cooling charging method
when OD ambient is greater than 70ºF
and less than 100ºF, indoor temp is
greater than 70ºF and less than 80ºF, and
line set is less than 80 ft.
2. Operate unit a minimum of 15 minutes before
checking the charge.
3. Measure liquid service valve pressure by
attaching an accurate gauge to the
service port.
4. Measure the liquid line temperature by
attaching an accurate thermistor type or
electronic thermometer to the liquid line
near the outdoor coil.
5. Refer to unit rating plate for required
subcooling temperature.
6. Find the point where the required subcooling
temperature intersects the measured liquid
service valve pressure.
7. To obtain the required subcooling temperature
at specific liquid line pressure, add refrigerant
if liquid line temperature is higher than indicated.
When adding refrigerant, charge in liquid form
using a flow restricting device into suction
service port. Recover refrigerant if temperature
is lower. Allow a tolerance of +/- 3ºF.
CONDENSING UNIT CHARGING INSTRUCTIONS
For use with units using R-410A refrigerant
REQUIRED LIQUID LINE TEMPERATURE
Required Subcooling
Temperature (ºF)
Liquid Pressure
at Service
Valve (psig)
68
10
12 14
16
251
259
266
274
283
291
299
308
317
326
335
345
354
364
374
76 74 72 70 68
78 76 74 72 70
80 78 76 74 72
82 80 78 76 74
84 82 80 78 76
86 84 82 80 78
88 86 84 82 80
90 88 86 84 82
92 90 88 86 84
94 92 90 88 86
96 94 92 90 88
98 96 94 92 90
100 98 96 94 92
102 100 98 96 94
104 102 100 98 96
384
395
406
416
427
439
450
462
474
106 104 102 100 98
108 106 104 102 100
110 108 106 104 102
112 110 108 106 104
114 112 110 108 106
116 114 112 110 108
118 116 114 112 110
120 118 116 114 112
122 120 118 116 114
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
114
116
118
120
122
124
Fig. 1 Wiring Diagram Model sizes 1--1/2 -- 5 tons, 208/230--1
Question and Answer IconNeed help?

Do you have a question about the Carrier Base Series and is the answer not in the manual?

Summary

Air Conditioner Wiring Diagrams

Connection Diagram Overview

Visual representation of electrical connections between components and power supply.

Schematic Diagram (Ladder Form)

Functional diagram illustrating circuit logic and component interconnections.

Condensing Unit Charging Instructions

Procedure for charging the unit with R-410A refrigerant using subcooling method.

Charging Data Table

Table correlating required liquid line temperature with subcooling for cooling only.

System Legend and Notes

Explanation of diagram symbols, important notes, and safety cautions.

Wiring Diagram for 208;230-3 and 460;3 Models

Connection Diagram for Specific Models

Illustrates wiring for 2-1/2 to 5 ton, 208/230-3 and 3 to 5 ton, 460/3 units.

Schematic Diagram for Specific Models

Functional circuit diagram for 2-1/2 to 5 ton, 208/230-3 and 3 to 5 ton, 460/3 units.

Charging Procedures and Safety

Details on refrigerant charging, notes, and cautions for specific models.

Wiring Diagram for 575;3 Models

Connection Diagram for 575;3 Unit

Wiring connections for the 3-5 ton, 575/3 model air conditioner.

Schematic Diagram for 575;3 Unit

Functional circuit diagram for the 3-5 ton, 575/3 model air conditioner.

Charging and Operational Guidance

Refrigerant charging, notes, and cautions specific to 575/3 units.

Overview

The 24ABB3 Base T™ Series Air Conditioner with Puron® is a robust and efficient outdoor unit designed for residential and light commercial cooling applications. It operates with R-410A refrigerant and is available in 1-1/2 to 5 nominal tons, with single and three-phase electrical configurations. The unit's primary function is to provide reliable cooling by transferring heat from the indoor space to the outdoors.

Function Description

At its core, the 24ABB3 air conditioner works by circulating refrigerant between an indoor coil (evaporator) and an outdoor coil (condenser), facilitated by a compressor and an outdoor fan motor. The compressor, a key component, pressurizes the refrigerant, causing it to absorb heat from the indoor air and release it to the outdoor air. The outdoor fan motor assists in dissipating this heat by drawing air over the condenser coil.

The unit incorporates several control and safety features to ensure optimal performance and protection. A contactor (CONT) is used to switch the main power to the compressor and outdoor fan motor, controlled by signals from the indoor thermostat. For single-phase units, a start capacitor (CAP) and start relay (SR) may be employed to provide the necessary torque for the compressor to begin operation, especially under heavy loads. A start thermistor (ST) can also be used in conjunction with the start capacitor for improved starting characteristics.

Safety mechanisms are integrated to prevent damage to the compressor and other components. A high-pressure switch (HPS) monitors the refrigerant pressure on the high-side of the system and will shut down the unit if pressure exceeds safe limits, indicating potential issues like a restricted condenser coil or overcharge. Conversely, a low-pressure switch (LPS) monitors the low-side pressure, shutting down the unit if it falls too low, which could indicate a refrigerant leak or restricted evaporator coil.

A compressor time delay (CTD) is included to prevent rapid cycling of the compressor. This delay ensures that the compressor remains off for a minimum of three minutes between cycles, allowing pressures to equalize between the high and low sides of the system. This equalization is crucial for reducing the starting load on the compressor and extending its lifespan.

For units operating in colder climates, a crankcase heater (CH) may be present. This heater warms the compressor oil during off-cycles, preventing refrigerant migration to the compressor crankcase, which can dilute the oil and lead to compressor damage upon startup. A crankcase heater switch (CHS) controls the operation of this heater.

Three-phase units include a Phase Rotation Monitor (PRM) with an LED indicator. This monitor is a critical safety feature that ensures the correct phasing of the 3-phase power supply. If the phasing is incorrect, the PRM will prevent the contactor from energizing, thus protecting the compressor from damage due to reverse rotation. The LED indicator provides visual feedback on the power status: off for no 24VAC, on for OK, and flash for a phase problem.

The unit also supports optional accessories like a liquid line solenoid valve (LLS), which can be used to control refrigerant flow to the indoor coil, and a discharge temperature switch (DTS), which monitors the compressor discharge temperature and can shut down the unit if it becomes too high, indicating potential overheating.

Usage Features

The 24ABB3 is designed for straightforward integration with an indoor thermostat, typically a cooling-only type. The wiring diagrams provide clear instructions for connecting the outdoor unit to the indoor thermostat and the external power supply. For systems with a transformer in the indoor section, specific guidance is given for connecting the grounded side to the BRN/YEL lead.

Charging the unit with R-410A refrigerant is a critical usage feature, and detailed instructions are provided for the subcooling charging method. This method is recommended when the outdoor ambient temperature is between 70°F and 100°F, and the indoor temperature is between 70°F and 80°F, with a line set less than 80 feet. The procedure involves measuring the liquid service valve pressure and the liquid line temperature near the outdoor coil using an accurate gauge and thermistor-type or electronic thermometer. The required subcooling temperature is referenced from the unit's rating plate. If the liquid line temperature is higher than indicated for a specific pressure, refrigerant should be added in liquid form using a flow-restricting device into the suction service port. Conversely, if the temperature is lower, refrigerant should be recovered. A tolerance of +/- 3°F is allowed for the temperature readings.

The unit's design emphasizes safe operation, with warnings against overcharging the system, which can lead to compressor damage. It is factory charged for most systems with matched coils and tubing up to 15 feet. For longer line lengths or specific indoor air flow rates, users are directed to the Product Data Literature for guidance on checking refrigerant charge for maximum efficiency.

Maintenance Features

Maintenance aspects are primarily focused on ensuring proper electrical connections and refrigerant charge. The manual stresses the importance of checking all electrical connections inside the control box for tightness. This helps prevent loose connections that could lead to intermittent operation or electrical faults.

In the event of system repair or final disposal, all refrigerant must be relieved and recovered. This involves using all service ports and opening all flow-control devices, including solenoid valves, if present. The manual explicitly prohibits venting refrigerant to the atmosphere, emphasizing the use of approved recovery equipment.

The unit's inherent thermal protection for the compressor and fan motor means these components are designed to shut down automatically if they overheat, providing a layer of self-protection. However, it is crucial not to operate the unit until service valves have been fully opened, as this can cause damage.

The compressor time delay, while a usage feature, also contributes to maintenance by protecting the compressor from wear and tear associated with rapid cycling. Users are reminded not to rapid cycle the compressor and to allow the three-minute off-time for pressure equalization.

For three-phase units, the Phase Rotation Monitor simplifies troubleshooting during installation or maintenance by immediately indicating if the power phasing is incorrect, preventing potential damage to the compressor. If a phase problem is detected, the solution is to simply interchange any two of the three power connections on the field side.

Overall, the 24ABB3 air conditioner is designed for reliable and efficient cooling, with built-in safety features and clear instructions for installation, operation, and maintenance, ensuring long-term performance and user safety.

Carrier Base Series Specifications

General IconGeneral
Sound LevelVaries by model
RefrigerantR-410A
Air Flow (Indoor)Varies by model
Dimensions (Indoor Unit)Varies by model
Dimensions (Outdoor Unit)Varies by model
Weight (Indoor Unit)Varies by model
Weight (Outdoor Unit)Varies by model
TypeSplit System
Power Supply208-230V, 1 Phase, 60Hz

Related product manuals