MAINTENANCE & REPAIR 19
CABINET TEMPERATURE CONTROL
Disconnect the power supply before
servicing the cabinet.
Remove the front grill.
The control is located in the machine compartment in
the upper righthand corner, just above the electrical
box. Control settings are numbered from #1 (warmest)
to #7 (coldest) positions.
The control capillary is inserted in a copper bulb well
just to the right of the control. The well is approximate-
ly 20" long and is secured to the cold wall evaporator.
The control reacts to the evaporator temperature which
is approximately -40°F in order to maintain a cavity
temperature of -20°F.
CAUTION:
COLD OUT NORMAL OUT NORMAL IN WARM IN
-30°F -23°F -15°F -2°F
TERMINALS: .25 QUICK CONNECT TAB
CAP TUBE LENGTH: 24"
1. Temperature Control
2. 115V Cabinet Power Switch (115V models)
3. 230V Cabinet Power Switch (230V models)