Carrier EHK2-05B - Electrical Data Tables

Carrier EHK2-05B
4 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
Table 5 Electric Heater Electrical Data for PSC Motor Units
Heat
Kit
Model
Used
on
Size
Nominal
Heat
Capacity
@ 240V
Ship-
ping
Weight
Heater
Capacity
(MBH)
Minimum
Circuit
Ampacity
(MCA)
MAX . Fuse
or Breaker
H e a t --- K i t
Ampacity
(HACR)
Min Wire
Size
(AWG)
Min Ground
Wire Size
Max Wire
Length (Ft)
‡‡
KW lbs. (kg) 208 240 208 240 208 240 208 240 208 240 208 240
EHK2-05B
1 --- 1 / 2
Ton
5
5.1 (2.3)
12.3 16.4 23.6 27.1 30 30 10 10 10 10 73 74
EHK2-08B 7.5 22.2 25.6 34.9 40.1 50 50 8 8 10 10 76 77
EHK2-10B 10 24.6 32.8 46.2 53.1 60 60 6 6 10 10 92 92
EHK2-05B
2
Ton
5
5.1 (2.3)
12.3 16.4 23.9 27.3 30 30 10 10 10 10 73 73
EHK2-08B 7.5 22.2 25.6 35.2 40.4 50 50 8 8 10 10 76 76
EHK2-10B 10 24.6 32.8 46.4 53.4 60 60 6 6 10 10 91 92
EHK2-05B
2 --- 1 / 2
Ton
5
5.1 (2.3)
12.3 16.4 24.2 27.7 30 30 10 10 10 10 72 72
EHK2-08B 7.5 22.2 25.6 35.5 40.7 50 50 8 8 10 10 75 76
EHK2-10B 10 24.6 32.8 46.8 53.7 60 60 6 6 10 10 91 91
EHK2-05B
3
Ton
5
5.1 (2.3)
12.3 16.4 24.9 28.3 30 30 10 10 10 10 70 71
EHK2-08B 7.5 22.2 25.6 36.2 41.4 50 50 8 8 10 10 74 74
EHK2-10B 10 24.6 32.8 47.4 54.4 60 60 6 6 10 10 90 90
* †† Copper wire must be used. If other than uncoated (non---plated), 75_C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger
than 10 AWG) is u sed, consult applicable tables of the National electric Code (ANSI/NGPA 70).
* ‡‡ Len gth shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
Table 6 Electric Heater Electrical Data for ECM Motor Units
Heat
Kit
Model
Used
on
Size
Nominal
Heat
Capacity
@ 240V
Ship-
ping
Weight
Heater
Capacity
(MBH)
Minimum
Circuit
Ampacity
(MCA)
MAX . Fuse
or Breaker
H e a t --- K i t
Ampacity
(HACR)
Min Wire
Size
(AWG)
Min Ground
Wire Size
Max Wire
Length (Ft)
‡‡
KW lbs. (kg) 208 240 208 240 208 240 208 240 208 240 208 240
EHK2-05B
1 --- 1 / 2
Ton
5
5.1 (2.3)
12.3 16.4 25 28.5 30 30 10 10 10 10 69 70
EHK2-08B 7.5 22.2 25.6 36.3 41.5 50 50 8 8 10 10 73 74
EHK2-10B 10 24.6 32.8 47.6 54.5 60 60 6 6 10 10 89 90
EHK2-05B
2
Ton
5
5.1 (2.3)
12.3 16.4 25 28.5 30 30 10 10 10 10 69 70
EHK2-08B 7.5 22.2 25.6 36.3 41.5 50 50 8 8 10 10 73 74
EHK2-10B 10 24.6 32.8 47.6 54.5 60 60 6 6 10 10 89 90
EHK2-05B
2 --- 1 / 2
Ton
5
5.1 (2.3)
12.3 16.4 26 29.5 30 30 10 10 10 10 67 68
EHK2-08B 7.5 22.2 25.6 37.3 42.5 50 50 8 8 10 10 71 72
EHK2-10B 10 24.6 32.8 48.6 55.5 60 60 6 6 10 10 87 88
EHK2-05B
3
Ton
5
5.1 (2.3)
12.3 16.4 26 29.5 30 30 10 10 10 10 67 68
EHK2-08B 7.5 22.2 25.6 37.3 42.5 50 50 8 8 10 10 71 72
EHK2-10B 10 24.6 32.8 48.6 55.5 60 60 6 6 10 10 87 88
* †† Copper wire must be used. If other than uncoated (non---plated), 75_C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger
than 10 AWG) is u sed, consult applicable tables of the National electric Code (ANSI/NGPA 70).
* ‡‡ Len gth shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
Copyright 2014 CAC / BDP / ICP D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 01/14
Manufacturer reserves the ri ght to change, at any time, specifications and designs without notice and without obligations.
C a t a l o g N o : A G --- E H K 2 --- 0 4
R e p l a c e s : A G --- E H K 2 --- 0 3