FMC5X, FMC5Z: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
11
Table 8 – PSC- SELECTING HEAT PUMP SPEED OF PSC MOTOR (Cased, Back Return))
-
Shaded boxes represent airflow outside the required 300-450 cfm/ton.
1. Airflow data includes electric heat and filter.
2. Use dry coil data for determining electric heater airflow.
3. Airflow data is with no return grill. When using a return grill on 18 & 24 sizes, decrease numbers above by approx. 10 CFM. For 30 & 36 sizes, decrease numbers above by approx. 50 CFM.
Table 9 – PSC- SELECTING HEAT PUMP SPEED OF PSC MOTOR (Cased, Bottom Return)
- Shaded boxes represent airflow outside the required 300-450 cfm/ton.
1. Airflow data is without filter or electric heat accessory. Heater adds 0.05-in. static.
2. Use wet coil data for determining electric heater airflow.
3. Use wet coil data for determining cooling airflow.
4. Accessory louver panel adds 0.05-in. Static.
Model Motor Speed
CFM Wet Coil without Filter or Electric Heat, Cased, Back Return
External Static Pressure-Inches W.C.[kPa]
[0] 0.05[.0125] 0.1[.025] 0.15[.0375] 0.2[.050] 0.25[.0625] 0.3[.075] 0.35[.0875]
18K
Low 698 674 646 620 582 527 457 361
Med - Factory
971 921 874 827 776 718 661 519
High
1034 985 934 882 820 759 683 565
24K
Low 698 674 646 620 582 527 457 361
Med - Factory
971 921 874 827 776 718 661 519
High
1034 985 934 882 820 759 683 565
Model Motor Speed
CFM Wet Coil without Filter or Electric Heat, Cased, Back Return
External Static Pressure-Inches W.C.[kPa]
[0] 0.1[.025] 0.15[.0375] 0.2[.050] 0.3[.075] 0.4[.100] 0.5[.125] 0.6[.150]
30K
Low - Factory 1193 1094 1005 932 840 828 734 627
Med
1301 1209 1109 1033 972 929 840 726
High
1419 1332 1219 1134 1070 1053 928 823
36K
Low 1193 1094 1005 932 840 828 734 627
Med - Factory 1301 1209 1109 1033 972
929 840 726
High
1419 1332 1219 1134 1070 1053 928 823
Model
Motor
Speed
CFM Wet Coil without Filter or Electric Heat, Cased, Bottom Return
External Static Pressure-Inches W.C.[kPa]
[0] 0.05[.0125] 0.1[.025] 0.15[.0375] 0.2[.050] .25[.0625] 0.3[.075] 0.35[.0875]
18K
Low 736 706 673 634 579 526 430 363
Med - Factory
959 914 860 802 738 658 587 467
High
997 956 907 846 775 700 614 512
24K
Low 736 706 673 634 579 526 430 363
Med - Factory
959 914 860 802 738 658 587 467
High
997 956 907 846 775 700 614 512
Model
Motor
Speed
CFM Wet Coil without Filter or Electric Heat, Cased, Bottom Return
External Static Pressure-Inches W.C.[kPa]
[0] 0.1[.025] 0.2[.050] 0.3[.075] 0.38[.095] .4[.100] 0.5[.125] 0.6[.150]
30K
Low - Factory 1168 1092 1009 928 860 845 760 616
Med
1272 1199 1117 1039 969 953 870 764
High
1396 1322 1251 1162 1083 1067 973 872
36K
Low 1168 1092 1009 928 860 845 760 616
Med - Factory 1272 1199 1117 1039 969 953
870 764
High
1396 1322 1251 1162 1083 1067 973 872