EasyManua.ls Logo

Carrier Infinity SYSTXCCUIZ01 - Advanced System Settings; Furnace and Fan Coil Settings; Heat Pump and AC Settings

Carrier Infinity SYSTXCCUIZ01
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMART RECOVERY:
On or Off, (default=On)
Applies to programmable operation only. Will start recovery 90
minutes prior to schedule change in both heating and cooling
mode.
ENGLISH/METRIC DISPLAY:
•°For°C, (default = °F)
RESET FACTORY DEFAULTS:
Program Schedule:
Yes/No to reset back to Energy Star default Time and Temp
schedules.
User Settings:
Yes/No to reset the user settings in the Advanced Setup to
factory default settings.
Install Settings:
Yes/No to reset install settings in Install/Service menus to
factory default settings.
Last 10 Faults:
Yes/No to reset last 10 faults under Service Info menu.
Setup = FURNACE:
Upon a first time start-up of the Infinity Zone Control, the
furnace DIP switch settings will be copied to the furnace setup
menu. Any changes can then be made from the Infinity Zone
Control.
AIRFLOW:
COMFORT (default)
EFFICIENCY
Selects the airflow of the furnace when heating. EFFICIENCY is
the airflow used to meet specified ratings, COMFORT is a
decreased airflow used to increase the output air temperature and
provide increased comfort.
AC AIRFLOW:
EFFICIENCY
COMFORT (default)
MAXIMUM
Selects the airflow of the furnace when cooling. COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY is the airflow used to meet specified ratings. MAXI-
MUM is a fixed airflow of 400 CFM/ton based on the outdoor unit
size.
DEHUM AIRFLOW:
NORMAL (default)
HIGH
NORMAL airflow adjustment is used during dehumidifying. If
duct sweating is an issue, selecting HIGH will increase the
dehumidifying airflow and reduce the sweating.
LOW HEAT RISE:
ON
OFF (default)
Set this to ON if the system contains a bypass humidifier. The ON
setting will increase the furnace low heat airflow.
STAGING:
SYSTEM (default)
LOW
HIGH
Controls the staging of the furnace. SYSTEM setting will allow
the Infinity Zone Control to determine furnace staging. LOW
will only run the low stage of furnace heat. HIGH will only run the
high stage of furnace heat.
OFF DELAY:
90 seconds
120 seconds (default)
150 seconds
180 seconds
Amount of time the blower will continue to run after heating has
shut off.
LOCKOUT TEMP:
NONE (default)
+5 to 55 deg F
Appears on dual fuel systems only (furnace with heat pump).
Outside temperature above which the furnace will NOT run.
Setup = FAN COIL:
HP/AC AIRFLOW:
EFFICIENCY
COMFORT (default)
MAXIMUM
Selects the airflow of the fan coil when heating or cooling with a
heat pump (or cooling with an AC unit). COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY is the airflow used to meet specified ratings. MAXI-
MUM is a fixed airflow speed of 400 CFM/ton based on the
outdoor unit size.
DEHUM AIRFLOW:
NORMAL (default)
HIGH
Normal airflow adjustment used during dehumidifying. If duct
sweating is an issue, selecting HIGH will increase the dehumidi-
fying airflow speed and reduce the sweating.
HEATER SIZE:
(choices dependent upon fan coil model)
This will show the heater size entered during the start-up process.
This value can be changed to another value (limited by the model
number of the fan coil). If the electric heater is self-identifying,
this value is not shown.
Setup = HEAT PUMP / AC:
COOLING LOCKOUT:
NONE (default)
45° F.
50° F.
55° F.
Outside temperature below which cooling will not be provided.
ENTERED SIZE:
(dependent on indoor unit model)
Size of the outdoor unit entered during the start-up process. If the
outdoor unit is a communicating model, this value will not be
shown. This size can be changed here but is limited to sizes that the
indoor unit can handle.
DEFROST INTERVAL:
30 minutes
60 minutes
90 minutes
120 minutes (default)
Time interval at which defrost cycles can occur on a heat pump.
9

Related product manuals