SYSTXCCUIZ01
Infinity™ Zone Control
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the
installation.
This symbol indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS.....................................................1
INTRODUCTION..........................................................................1
INSTALLATION AND START-UP OVERVIEW......................1
INSTALLATION...........................................................................2
INITIAL POWER-UP....................................................................5
QUICK START..............................................................................7
INSTALL / SERVICE MENUS....................................................8
OPERATIONAL INFORMATION.............................................13
TROUBLESHOOTING ...............................................................14
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform
to local and national electrical codes. Improper wiring or installa-
tion may damage the Infinity™ Zone System. Recognize safety
information. This is the safety-alert symbol
. When you see this
symbol on the equipment and in the instruction manual, be alert to
the potential for personal injury. Understand the signal words
DANGER, WARNING, and CAUTION.
These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards, which will result in severe
personal injury or death. WARNING signifies a hazard, which
could result in personal injury or death. CAUTION is used to
identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which may result in enhanced installation, reliability,
or operation.
INTRODUCTION
The Infinity Zone System consists of several intelligent commu-
nicating components which includes the Infinity Zone Control (or
User Interface), Smart Sensors, Damper Control Module, variable-
speed furnace or FE fan coil, 2-speed AC or HP, which continually
communicate with each other via a four-wire connection called the
ABCD bus. Commands, operating conditions, and other data are
passed continually between components over the ABCD bus. The
result is a new level of comfort, versatility, and simplicity.
All Infinity furnaces or fan coils are variable-speed and multi stage
for maximum flexibility, efficiency, and comfort. They support
controlled ventilation, humidification, dehumidification, and air
quality control. Either an Infinity dual capacity (communicating),
or a standard 24 vac controlled outdoor unit may be used.
When using conventional outdoor units, the Infinity furnace or fan
coil provides the 24 volt signals needed to control them. Also, the
Infinity™ Damper Control Module (P/N SYSTXCC4ZC01) al-
lows connection of a conventional HRV or ERV without the need
for a separate wall control.
All system components are controlled through the wall mounted
Infinity™ Zone Control, which replaces the conventional thermo-
stat and provides the homeowner with a single wall control for all
features of the system.
INSTALLATION AND START-UP OVERVIEW
This instruction covers installation of the Infinity™ Zone Control
only. Physical installation instructions for the indoor and outdoor
equipment, Damper Control Module, and accessories are provided
with each unit.
Setup, commissioning, operation, and troubleshooting of the
Infinity Zone System is covered only in this installation instruc-
tion. It is the guide to connecting the system components and
commissioning the system once all physical components are
installed. Special screen prompts and start-up capabilities are
provided in the Infinity System to simplify and automate the initial
commissioning of the system.
Install Infinity™ Zone Control according to this instruction.
Install indoor unit, outdoor unit, and accessories according to
their instructions.
Wire complete system according to this instruction.
Setup, commission, and operate system according to this
instruction to assure a smooth and trouble free start-up.
HOLD
COOL
HEAT
OFF
ZONE
INFINITY
SYSTEM
Infinity™ Zone Control
SYSTXCCUIZ01
A03149
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab misc. misc.
PC 101 Catalog No. 809-50025 Printed in U.S.A. Form UIZ01-1SI Pg 1 03-04 Replaces: NEW

Questions and Answers

  • B
    Benjamin DavidAug 1, 2025
    How to troubleshoot Carrier Infinity SYSTXCCUIZ01 Temperature Controller Infinity Zone Control™ when it does not power up?
    • M
      marissa34Aug 1, 2025
      If your Carrier Infinity Zone Control™ does not power up, there are several things you can check: * Recheck the wiring to ABCD on all devices, ensuring that all colors match for every terminal. * Make sure power is applied to the indoor unit and that the amber LED is lit on the indoor control circuit board. * Check for 24VAC between the C and D terminals at the Infinity Zone Control™ terminal connector and Damper Control Module. * Also, check the fuse on the indoor unit’s circuit board.
  • W
    William StewartAug 6, 2025
    What to do if my Carrier Temperature Controller display says 'Indoor Unit Not Found'?
    • C
      Casey SnyderAug 6, 2025
      If your Carrier Temperature Controller displays '?Indoor Unit Not Found?', try the following: * Recheck the wiring to ABCD on all devices, ensuring all colors match for every terminal. * Press the left-side button to try again. * If the display continues to show the same message, disconnect all devices from ABCD and connect the User Interface directly to the indoor unit.
  • C
    Christina WrightAug 10, 2025
    How do I restart Carrier Infinity SYSTXCCUIZ01 Temperature Controller if I made a mistake on the start-up screens?
    • Q
      qramirezAug 10, 2025
      To return to the start-up screens on your Carrier Temperature Controller after accidentally entering run mode: * Press the ADVANCED button for at least 10 seconds to access the Install/Service menu. * Scroll down to the INSTALL selection and press the right-side button. The screen will then prompt you to press the right side again to reinstall the system. * Also, ensure that zone module 5 - 8 has the DIP switches set to the right and zone module 1 - 4 has the DIP switches set to the left. * Recheck wiring to the ABCD connectors.
  • M
    millermelissaAug 16, 2025
    What to do if Carrier Infinity SYSTXCCUIZ01 Temperature Controller display says 'Outdoor Unit Not Found'?
    • M
      Misty RichmondAug 16, 2025
      If your Carrier Temperature Controller displays '?Outdoor Unit Not Found?' and you have a two-speed communicating outdoor unit, consider the following: * Recheck the wiring to the ABCD connector on the outdoor unit, ensuring all colors match for every terminal. * Check for 24VAC between the C and D terminal connector of the outdoor unit.
  • K
    Kristin KingAug 20, 2025
    Why some zones in my Carrier Infinity SYSTXCCUIZ01 zoned system do not provide enough comfort?
    • K
      Kathleen BrownAug 20, 2025
      If some zones in your Carrier Temperature Controller zoned system aren't providing enough comfort, the zone airflow limit may be set too low. Perform the Zone Airflow Limit Checkout procedure and raise the airflow limit setting, if possible.
  • F
    frankjacksonAug 26, 2025
    What to do if some zones provide too much airflow and are noisy in Carrier Temperature Controller?
    • D
      Diana Garcia DVMAug 26, 2025
      If some zones in your Carrier Temperature Controller provide too much airflow and are noisy, it may be because the zone airflow limit is set too high. You should perform the Zone Airflow Limit Checkout procedure and lower the airflow limit setting if possible.

Summary

Safety Considerations

Installation and Start-Up Overview

Installation Steps

Zone Control Location and Sensor Placement

Guidelines for optimal placement of the Infinity Zone Control and sensors for accurate temperature readings.

Wiring and Module Installation

Wiring considerations, ABCD connector use, Damper Control Module location, and mounting options for the Zone Control.

Installing the Infinity Zone Control

Wiring Diagrams and Equipment

ABCD Connector and Wiring Standards

Details on the 4-wire ABCD connector, recommended color coding, and general wiring practices.

Equipment Wiring Diagrams

Diagrams illustrating connections for various indoor and outdoor equipment configurations.

System Configuration and Setup

Power Up Sequence and Communication

The initial process of powering up the system and establishing communication with equipment.

Selecting System Components

Outdoor Unit Selection

Procedure for identifying and selecting the type and size of the outdoor unit.

Zone Equipment Identification

Process for identifying and confirming zone equipment, including sensors.

Setup Completion and Duct Assessment

Equipment Summary and Save

Reviewing the summary of installed equipment and saving all selections for the system.

Duct Assessment Procedure

Measuring duct capacity and airflow for each zone to optimize system performance.

Install;Service Menus

Accessing Install;Service Menus

Procedure to enter and navigate the Install/Service menus for system configuration.

Setup Menu Options

Configuration settings for Thermostat, Furnace, Heat Pump, Zoning, and Accessories.

Advanced System Settings

Zoning and Accessory Configuration

Equipment Checkout Procedures

Service Information and Status

Troubleshooting Common Issues

System Malfunction and Error Codes